(5) Operation data during emergency operation
During emergency operation, no communication is performed with the indoor unit, so the data items needed for operation
are set to the following values:
Operation data
Intake temperature (TH1)
Indoor fl uid pipe temperature (TH2)
Indoor 2-phase pipe temperature (TH5)
Set temperature
Outdoor fl uid pipe temperature (TH3)
Outdoor 2-phase pipe temperature (TH6)
Outdoor air temperature (TH7)
Temperature difference code
(intake temperature - set temperature) (∆Tj)
Discharge super heat (SHd)
Sub-cool (SC)
w1: If the thermistor temperature data is normal (not open/short), that data is loaded into the control as valid data.
When the unit enters emergency operation and TH values are mismatched, set the thermistors to open/short.
And the unit runs emergency operation with the values listed above.
w2: If one thermistor is set to open/short, the values of SHd/SC will be different from the list above.
[Example] When liquid temperature thermistor (TH3) has an open or short circuit.
Thermistor
TH3
45:, 113°F
TH6
Regard normal fi gure as effective data.
TH32
Regard normal fi gure as effective data.
TH5
TH2
Discharge superheat (SHd)
Cooling = TH32 - TH6 = Tc - Ta
Heating = TH32 - TH5 = Td - (50: or 122°F)
Degree of subcooling (SC)
Cooling = TH6 - TH3 = Ta - (45: or 113°F)
Heating = TH5 - TH2 = 50: - 45: = 5 ˚C.
or
= 122°F - 113°F = 9˚F
OCH512
COOL
HEAT
5:, 41°F
Ta
Tb
Tc
Td
5:, 41°F
50:, 122°F
5:, 41°F
45:, 113°F
Operation mode
COOL
27:, 81°F
20.5:, 69°F
5:, 41°F
45:, 113°F
5:, 41°F
50:, 122°F
25:, 77°F
22:, 72°F
45:, 113°F
5:, 41°F
50:, 122°F
5:, 41°F
35:, 95°F
7:, 45°F
5
30˚C, 54˚F
30˚C, 54˚F
5˚C, 9˚F
53
Remarks
HEAT
(w1)
(w1)
(w1)
5
(w2)
5˚C, 9˚F
(w2)