Fault Finding (Chart 5 & 6) - Rheem 52S160 Service Instructions Manual

Solar hiline water heater
Table of Contents

Advertisement

Fault Finding (Chart 5 & 6)
5
Is the water temperature
at the hot tap above
75ºC?
YES
Is there a plumbing leak
or dripping hot tap
causing inlet cold water to
open Sunstat valve?
6
Is boosting required
during periods of high
solar gain to meet hot
water demands?
NO
Are there any water leaks
around the collectors or
heater?
NO
Is the booster circuit
connected to an off peak
tariff?
NO
Does the customer boost
only when required?
TM005 Rheem Solar Hiline Service Instructions REV D
D.O.I 20/02/2009
This document is stored and maintained electronically by
Water too hot - Collector Circuit
Warning:
Water under pressure and at temperatures up to
150ºC may be present in the collector. Isolate water
supply and relieve pressure through a hot tap prior to
opening the collector pipe work.
NO
Is the leak, discharge
YES
from the T&PR valve?
YES
Service. All printed copies not bearing this statement in RED are deemed "uncontrolled".
NO
YES
High energy bills
YES
YES
YES
NO
23
Advise customer on operation of
solar system and benefits of
storing water at 70ºC.
Tempering valves should be considered
for ablution areas if concerns surround
small children or elderly occupants.
Repair plumbing leaks or dripping
taps and check ECO on
thermostat is not tripped.
Replace Sunstat valve and check
ECO on thermostat is not tripped.
Rectify leaks at connectors or
NO
fittings. Replace collector or tank
if leaking.
3.1
Suggest a usage pattern that will
minimise depletion of hot water
supply at night.
Advise customer to operate
booster only when required or
switch to an off peak tariff.
2
3