14.2. Self-diagnosis Method

14.2.1. Heater 2 Temperature Sensor Abnormality (H32)
Malfunction Decision Conditions:
During startup and operation of heating, the temperatures detected by the heater 2 temperature sensor are used to determine
sensor error.
Malfunction Caused:
1. Faulty connector connection.
2. Faulty sensor.
3. Faulty water tank unit PCB.
Abnormality Judgment:
Continue for 5 seconds.