Panasonic WH-TX30B9E8 Service Manual page 29

Tank unit for central heating system
Hide thumbs Also See for WH-TX30B9E8:
Table of Contents

Advertisement

Item code
Display
Hot water supply
temperature
H87
abnormal
Hot water supply
flow adjust valve
H59
abnormal
Remocon/Tank error
H76
Abnormality detection condition
Hot water supply temperature (TH5)
above 60qC for 30sec, at condition
where water fully open is detected.
Step 1 (normal): During hot water
supply, hot water supply, hot water
supply temp (TH5) is hot water
setting temp. +10k. When above
mentioned condition continues for
30sec., shift to Step 2.
Step 2 (normal): Control to fully close
at flow adjust valve. When it is at full
close position, shift to Step 3. During
full close control, check hot water
supply temp. (TH5), if hot water
supply temp. is below setting temp.
+10k, shift to Step 1.
Step 3 (normal): When condition of
hot water supply temp. (TH5) is
above setting temp. +10k has
continued for 30sec., check hot water
supply temp. abnormality (H87).
Step 1 (normal): When operate to
water side with Maximum speed
(250pps), do the "valve fully open to
water side sequence" for 45sec. and
if cannot detect water full open
position, shift to step 2.
Step 2: Stop PUMP 1
Step 3: Do the "valve fully open to
water side sequence" for 45sec. and
if still cannot detect water full open
position, shift to step 2.
Error is detected.
During hot water supply (Flow SW
ON), it is at open side full open
position, and when origin point
position detection is not OFF.
After origin point is detected, when
origin point position detection is not
OFF and operate above INT (300)
pulses at control to operate towards
full open side.
No receiving data for 1 min.
Operation when
Detection period
Stop hot water supply
operation (stop hot
water supply pump).
During hot water supply
Operate flow adjust
valve to close side for
6200(1838h) pulse
Stop hot water supply
operation (Close flow
During hot water supply
adjust valve to full
position, stop hot water
When hot water mixing
valve operate to water
side with Maximum
Stop hot water supply
speed (250pps)
operation (stop hot
• initial start
water supply pump).
• operation SW turn off
Stop hot water supply
• error occur and
flow adjust valve
operate towards full
close
• Control for later boil
action
Stop hot water supply
During hot water supply
Stop hot water supply
(Detection time: 5sec.)
flow adjust valve
Stop hot water supply
Initial reset control.
After move to close
Once a day reset
side for 6200 (1383h)
control.
pulse, stop hot water
supply flow adjust
valve operation.
29
Cancel condition
abnormal
Cancel by reset power
(not canceled by error
reset SW)
Cancel by reset power
(not canceled by error
reset SW)
supply pump).
Operate error reset SW.
Cancel by reset power.
operation *10.
operation.
Operate error reset SW.
Cancel by reset power.
operation.
operation.
Cancel by reset power.