* Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
Note: See unit Installation Instruction for proper installation.
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessive capacity loss. The suction line
diameters shown in the chart below are acceptable for AC systems with Puron refrigerant:
Unit
Maximum
Vapor Line
Nominal
Liquid Line
Diameters
Size
Diameters
(In.) OD
(Btuh)
(In. OD)
24,000
5/8
2 ---Stage
3/8
HP with
3/4
Puron
36,000
5/8
2 ---Stage
3/8
3/4
HP with
Puron
7/8
48,000
3/4
2 ---Stage
3/8
7/8
HP with
Puron
1 ---1/8
60,000
3/4
2 ---Stage
3/8
7/8
HP with
Puron
1 ---1/8
Standard Length = 80 ft. (24.4 m) or less total equivalent length
Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines
Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit.
— Applications in this area are not recommended due to insuficient oil return.