Flue Gas Test - Wolf CGG-1K-24 Installation And Operating Instructions Manual

Gas fired wall mounted boiler
Table of Contents

Advertisement

The flue gas emissions must be tested with the boiler closed.
Testing the combustion air
- Remove the screw from the test port "inlet air".
- Open the gas shut-off valve.
- Inset the test probe until it bottoms out.
- Start the boiler and turn the heating water temperature selector
to emissions test [chimney sweep symbol]. (The illuminated
status display ring flashes yellow.)
- Test the temperature and CO
The balanced flue pipe is not sound if the CO
rectify the leak.
- After the test has been completed, switch the boiler OFF,
remove the test probe and close the test port. Ensure the
screws are seated firmly.
Testing the flue gas parameters
Flue gas can escape into the installation room,
if the test port is left open. This results in a
risk of asphyxiation.
- Remove the screw from the test port "flue gas".
- Open the gas shut-off valve.
- Inset the test probe until it bottoms out.
- Start the boiler and turn the heating water temperature selector
to emissions test [chimney sweep symbol]. (The illuminated
status display ring flashes yellow.)
- Inset the test probe into the centre of the pipe.
- After the test has been completed, switch the boiler OFF,
remove the test probe and close the test port. Ensure the
screws are seated firmly.
3 2

Flue gas test

value.
2
content ≥ 0.3 %;
2
Vertical boiler flue connection
Horizontal boiler flue connection
Manifold with test port Ø 80/80
3062087_0207

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cgg-1k-28

Table of Contents