Vent Requirements

The gas appliance and vent system must be vented directly to the outside of the building, and never be
attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent gas appliance
must use its own separate vent system.
In addition to the requirements listed here, follow the requirements provided with the vent.
A firestop is required whenever the vent penetrates a wall, floor, or ceiling (passes through framing
members). Horizontal vent less than 48" (1219mm) above the fireplace must use the Travis Firestop (sku
93006094 - it incorporates a 3" (76mm) clearance above, 1" (25mm) clearance below and to the sides of the
vent). Other penetrations only require a 1" (25mm) clearance and may use a standard firestop (make sure
the required 1" (25mm) clearance is met).

Vent Clearances

The vent must maintain the required clearance to combustible materials to prevent a fire. Do not fill air
spaces with insulation.
Sides
Above
Below Horizontal or 45° Section
Vertical Termination
Use a roof flashing and storm collar
whenever passing through the roof
Use a firestop whenever
passing through a ceiling
Use a support box
on exposed vent

Altitude Considerations

This heater has been tested at altitudes ranging from sea level to 6,000 feet (1800 M). In this testing we have found that
the heater, with its standard orifice, burns correctly with just an air shutter adjustment.
Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard. Consult your
dealer or installer if you suspect an improperly adjusted air shutter.
© Travis Industries
Installation
(for qualified installers only)
Before 48" (1219mm) Rise
4090507
1" (25mm)
3" (76mm)
1" (25mm)
Required Firestop
Min. 1"(25mm)
Min. 1" (25mm)
After 48" (1219mm) Rise
1" (25mm)
1" (25mm)
1" (25mm)
Horizontal
Termination
Min. 3" (76mm)
(1" or 25mm if a
minimum 48"or
1219mm above the
fireplace)
Min. 1" (25mm)
100-01217_000