Follett 12 Series Installation, Operation And Service Manual page 18

220v 60hz/230v 50hz ice and water dispensers
Table of Contents

Advertisement

Normal operation – Stage 4
Once the ice level control opens, the B-E LED goes out. After a 10 second delay the compressor LED (C),
compressor and fan motor go off. (Should the ice level control not remain open for 10 seconds, the icemaker
will continue to run.) The gearmotor continues to run and the DR LED remains on for 60 seconds. The purpose
of this function is to drive the remaining ice out of the evaporator and to boil off any refrigerant remaining in the
evaporator. The bin timer LED (BT) comes on, starting the twenty minute off cycle time delay.
GRND IN
ELEC BOX
GREEN/YELLOW
G
BROWN
L
BLUE
N
START
CAPACITOR
RUN
CAP.
ORANGE
BLACK
M
FAN
4
WHITE
WHITE
Normal operation – Stage 5
The drive motor now shuts down and the DR LED is off. The B-T LED remains on for 20 minutes. The icemaker
will not start while the B-T LED is on. To restart the icemaker for troubleshooting purposes, depress the reset
button to clear the control board.
GRND IN
ELEC BOX
GREEN/YELLOW
G
BROWN
L
BLUE
N
START
CAPACITOR
RUN
CAP.
ORANGE
BLACK
M
FAN
4
WHITE
WHITE
WATER
SENSOR
WHITE
BLACK
WHITE
RED
POTENTIAL
5
START RELAY
BLACK
2
1
ORANGE
T.O.L.
RED
S
C
R
COMPRESSOR
BLACK
2
BLACK
START
RUN
YELLOW
3
GEARMOTOR
WATER
SENSOR
WHITE
BLACK
WHITE
RED
POTENTIAL
5
START RELAY
BLACK
2
1
ORANGE
T.O.L.
RED
S
C
R
COMPRESSOR
BLACK
2
BLACK
START
YELLOW
RUN
3
GEARMOTOR
L1
L2
COMP
FAN
DRV
BLACK
T.O.L.
L1
L2
COMP
FAN
DRV
BLACK
T.O.L.
18
DISPENSER
POWER
BIN
T-STAT
DR
C
20M
BIN
60M
SIGNAL
SWITCH
2ND
WTR
B-T
B-E
COMPRESSOR
SWITCH
HIGH PRESSURE
SAFETY SWITCH
BLACK
DISPENSER
POWER
BIN
T-STAT
DR
C
20M
BIN
60M
SIGNAL
SWITCH
2ND
WTR
B-T
B-E
COMPRESSOR
SWITCH
HIGH PRESSURE
SAFETY SWITCH
BLACK

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents