Condensate Drain; Wiring; Power Supply - Rheem RKNA SERIES Installation Instructions Manual

Package gas electric 3-5 tons
Table of Contents

Advertisement

TABLE 3
METER TIME IN MINUTES AND SECONDS FOR NORMAL
INPUT RATING OF FURNACES EQUIPPED FOR NATURAL
OR LP GAS
METER
HEATING VALUE OF GAS BTU PER CU. FT.
INPUT
SIZE
900
BTU/HR
CU. FT.
MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC.
ONE
1
21
40,000
TEN
13
30 15
ONE
0
54
60,000
TEN
9
0 10
ONE
0
41
80,000
TEN
6
45
ONE
0
33
100,000
TEN
5
24
1000
1040
1100
2500
1
30
1
34
1
39
3
0 15
36 16
30
37
1
0
1
3
1
6
2
0 10
24 11
0
25
0
45
0
47
0
50
1
7
30
7
48
8
15
18
0
36
0
38
0
40
1
6
0
6
15
6
36
15
NOTICE: DERATING OF THE HEATING INPUT FOR HIGH ALTITUDE IN THE FIELD
IS UNLAWFUL IN CANADA (REFER TO CAN/CGA 2.17). UNITS INSTALLED IN
ALTITUDES GREATER THAN 2,000 FEET (610 METERS) MUST BE SHIPPED FROM
THE FACTORY OR FROM A FACTORY AUTHORIZED CONVERSION STATION
WITH THE HEATING INPUT DERATED BY 10% SO AS TO OPERATE PROPERLY IN
ALTITUDES FROM 2,000 - 4,500 FEET (610 - 1,373 METERS).
E.CONDENSATE DRAIN
The condensate drain connection of the evaporator is threaded 3/4 nominal P.V.C.
pipe. IMPORTANT: Install a condensate trap to ensure proper condensate drainage.
See Figure 16.
IX. WIRING
A. POWER SUPPLY
WARNING
!
TURN OFF THE MAIN ELECTRICAL POWER AT THE BRANCH CIRCUIT DIS-
CONNECT CLOSEST TO THE UNIT BEFORE ATTEMPTING ANY WIRING. FAIL-
URE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL
INJURY OR DEATH.
1. All wiring should be made in accordance with the National Electrical Code.
Consult the local power company to determine the availability of sufficient power to
operate the unit. Check the voltage at power supply to make sure it corresponds to
the unit's RATED VOLTAGE REQUIREMENT. Install a branch circuit disconnect
near the rooftop, in accordance with the N.E.C., C.E.C. or local codes. A bracket is
provided with the unit for mounting of the disconnect. See Figure 17.
2. It is important that proper electrical power is available at the unit. Voltage should not
vary more than 10% from that stamped on the unit nameplate. On three phase units,
phases must be balanced within 3%.
3. For branch circuit wiring (main power supply to unit disconnect), the minimum wire size
for the length of run can be determined from Table 3 using the circuit ampacity found on
the unit rating plate. Use the smallest wire size allowable in Table 4 from the unit dis-
connect to unit.
NOTE: A bracket is provided with the unit for mounting the branch circuit disconnect to
the unit. This is the recommended location for the disconnect. See Figure 17.
4. For through the base wiring entry reference Figure 18. All fittings and conduit are field
supplied for this application. Reference the chart with Figure 18 for proper hole and
conduit size.
FIGURE 16

CONDENSATE DRAIN

45
30
30
0
53
45
DO NOT OVERTIGHTEN DRAIN FITTING
30
0
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents