Heating Sequence - Lennox G40UH Series Installation Instructions Manual

G40uh series
Hide thumbs Also See for G40UH Series:
Table of Contents

Advertisement

HEATING
SEQUENCE
CONTINUED
NORMAL HEATING MODE
ABNORMAL
HEATING MODE
15-SECOND
COMBUSTION
AIR INDUCER PREPURGFI9
INITIATED BY CLOSED PRESSURE
SWITCH.
I
YES
NO
I
IGNITER WARM-UP -- 20 SECONDS.
I'_1
YES
4-SECOND TRIAL FOR IGNITION.
GAS VALVE OPENS. IGNITER ENERGIZED FOR
UP TO 4 SECONDS.
,4
I
I
I
YES
FLAME STABILIZATION
PERIOD.
4 SECONDS
_
FLAME RECTIFICATION
CURRENT
CHECK. CAN FLAME BE PROVEN WITHIN
4 SECONDS AFTER GAS VALVE OPENS?
(0.5 microamps)
YES _
FLAME PRESENT?
YES
1
FLAME SIGNAL 1.5 MICROAMPS
OR GREATER?
YES
_
INDOOR BLOWER ON
AFTER 45-SECOND
DELAY
YES
_1
PRIMARY AND SECONDARY
LIMIT
SWITCHES
CLOSED?
YES
I
ROLLOUT SWITCH CLOSED?
YES
_'I
COMBUSTION
AIR PRESSURE
SWITCH
CLOSED?
YES
I
THERMOSTAT
DEMAND SATISFIED.
YES
I
LED #1 & #2 SIMULTANEOUS
SLOW FLASHES.
YES
COMB. AIR INDUCER CONTINUES
5-SECOND
POST PURGE AFTER T'STAT DEMAND IS SATISFIED.
INDOOR AIR BLOWER COMPLETES
SELECTED
[
OFF DELAY BEFORE SHUTT NG OFF.
IS VOLTAGE ABOVE 90 VOLTS?
YES
LEDS SIGNAL
ALTERNATING
FAST FLASH UNTIL
VOLTAGE IS ABOVE
95 VOLTS, THEN
RESTARTS HEATING
SEQUENCE.
GAS VALVE OFF. COMBUSTION
AIR INDUCER ON.
INDOOR BLOWER OFF.
I
NO
HAS CONTROL
FAILED TO SENSE FLAME FOR
I
HEAT DEMAND?
F VE CONSECUT
VE TR ES DUR NG A S NGLE
_t
ES
I__
WATCHGUARD
MODE. GAS VALVE OFF.
I_
COMBUSTION
AIR INDUCER OFF.
INDOOR BLOWER OFF WITH DELAY
LEDs SIGNAL WATCHGUARD
FAILURE CODE.
IS 60-MINUTE
RESET PERIOD COMPLETE?
_t
HAS CONTROL RESET IGNITION
pI
NO
SEQUENCE
FOUR TIMES?
YES
I
LOW FLAME SIGNAL
LIMIT SWITCH WATCHGUARD
(Does not affect operation of control)
MODE. GAS VALVE, COMB. AIR
LED #1 -- SLOW FLASH
INDUCER AND INDOOR BLOW-
LED #2 -- FAST FLASH
ER OFF. LEDs SIGNAL LIMIT
SWITCH OPEN UNTIL MAIN
POWER IS
I
GAS VALVE DE-ENERGIZED.
INTERRUPTED OR
I COMBUSTION
AIR INDUCER DE-ENERGIZED.
I
T'STAT IS CYCLED
I NO I INDOOR BLOWER ON UNTIL SWITCH CLOSES. I
OFF/ON FOR 1
LED #1 -- SLOW FLASH. LED #2 -- ON.
I
SEC. MINIMUM.
I
I
IS LIMIT SWITCH CLOSED?
I
60-MINUTE WATCH-
GUARD PERIOD
YES
STARTS AT TIME
I
HAS PRIMARY / SECONDARY
IYES
LIMIT CLOSES.
LIMIT RESET TIME
_
IS 60-MIN PERIOD
EXCEEDED
3 MINUTES?
COMPLETE?
I NO
NO
GAS VALVE POWER OFF.
COMBUSTION
AIR INDUCER POWER ON.
INDOOR BLOWER ON
LED #1 -- ON. LED #2 -- SLOW FLASH.
SEQUENCE
HOLDS UNTIL ROLLOUT SWITCH IS RESET
AND MAIN POWER IS INTERRUPTED
OR
__'_NI_.._,
THERMOSTAT
IS CYCLED OFF/ON FOR 1 SEC. MINIMUM.
I
i
GAS VALVE DE-ENERGIZED.
COMBUSTION
AIR INDUCER ON.
YES
I
INDOOR BLOWER OFF WITH DELAY
LED #1 -- OFF. LED #2 -- SLOW FLASH.
I
I HASCAB SWITCH CLOSED IN2.5MINUTES? I
I
NO
I
5"M'NUTE
PRESSURE
SW'TCHI
WATCHGUARD
MODE.
b
Page 32