BRINE VALVE "A" DIMENSION
The brine valve contains a float-actuated safety shut-off device to prevent overflow of the brine tank in the unlikely
case of an electrical or mechanical failure during the brine tank refill cycle.
It is recommended that the brine valve float be used as intended, that is, as a secondary, safety shut off. Remember,
the timer mechanism provides the primary refill shut-off. To use the float as a safety shut-off, refer to Table 4 for
the salt dosage and brine tank size being used. The "A" dimension is the distance between the filter screen and the
bottom of the float (Figure 2) when the float stem is in its fully raised position; adjust the float and rubber grommets
accordingly.
FIG. 2
10
CULLIGAN MEDALLIST SERIES