External Output Terminal Wiring; Wiring For External Output - Toyotomi HC-20 Installation And Operation Instructions Manual

Heat convector
Table of Contents

Advertisement

HC-20_US.qxd 14.7.1 9:13 ページ 7
This unit has an External output terminal for low-voltage (24 volts or less) contacts to connected to a circulation
pump control or zone valve. When connecting the circulation control or zone valve unit to this terminal, it is possible
to stop the circulation by the output from internal contact switch in the Heat convector. When the
ON and there is a call for heat, the internal contact switch is closed. When
temperature reaches 4 degrees above Set temperature the internal contact switch is open.
1. Remove the four (4) screws and the cover on the back side of the unit.
2. Cut the rubber bushing of the cover by a cutter and insert the wire for the circulation control or zone valve.
3. Connect the wire to the terminal block in accordance with the color indication.
4. Fix the cover to the unit with the four (4) screws.
Rubber bushing
After installation is completed, secure the unit to the wall with the wall fixing kit provided with the unit.
NOTE: Make sure the unit is parallel to the wall.
7

EXTERNAL OUTPUT TERMINAL WIRING

WIRING FOR EXTERNAL OUTPUT

Cover
Note: Use at least
AWG 18 wire.
[ EXTERNAL OUTPUT SPECIFICATIONS ]
Contact Rating
3A 24VAC
Maximum Switching Voltage
30VDC
Maximum Carrying Current
5A
Maximum Switching Power
90W
Minimum Switching load
10mA 5VDC
Power switch is OFF or the Room
External output terminal
Universal Switching Relay,
Control or Zone Valve.
24 VAC
24 VAC
Cover
Wall bracket A
Wall bracket B
Wooden screw
Power switch is
POWER SUPPLY
120VAC
CIRCULATION
WATER PUMP