Hitachi L2002 Series Quick Reference Manual page 25

L2002 series
Hide thumbs Also See for L2002 Series:
Table of Contents

Advertisement

Func.
Code
B021/
Overload restriction operation mode
B221
• 00 Disabled
• 01 Enabled for accel and constant speed
• 02 Enabled for constant speed only
B022/
Overload restriction setting
B222
B023/
Deceleration rate at overload restriction
B223
B031
Software lock mode selection
• 00 Low-level access, [SFT] blocks edits
• 01 Low-level access, [SFT] blocks edits
(except F001 and Multi-speed parameters)
• 02 No access to edits
• 03 No access to edits except F001 and Multi-
speed parameters
• 03 High-level access, including B031
B080
[AM] analog signal gain
B082
Start frequency adjustment
B083
Carrier frequency setting
B084
Initialization mode (parameters or trip history)
• 00 Trip history clear
• 01 Parameter initialization
• 02 Trip history clear and parameter
initialization
B085
Country code for initialization
• 00 Japan version
• 02 USA version
B086
Frequency scaling conversion factor
B087
STOP key enable
• 00 Enable
B088
Restart mode after FRS
• 00 Restart from 0Hz
• 01 Restart from frequency detected from
actual speed of motor
B089
Monitor display select for networked inverter,
7 options:
• 01 Output frequency monitor
• 02Output current monitor
• 03 Rotation direction monitor
• 04 Process variable (PV), PID feedback
monitor
• 05 Intelligent input terminal status
• 06 Intelligent output terminal status
• 07 Scaled output frequency monitor
Name / Description
• 01 Europe version
• 01 Disable
23
Default
Set
Value
Value
–FE(F)/–FU
01
Rated
current x 1.5
1.0 / 30.0
01
100.
0.5
5.0
00
01 / 02
1.0
00
00
01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents