VENT SYSTEM
This furnace is certified to be installed with one of two possible vent
configurations.
1.
Horizontal vent system. This vent system can be installed com-
pletely horizontal or combinations of horizontal, vertical, or offset
using elbows.
2.
Vertical vent system. This vent system can be installed completely
vertical or a combination of horizontal, vertical, or offset using
elbows.
VENT APPLICATIONS AND TERMINATION
When selecting the location for a horizontal combustion air / vent termi-
nation, the following should be considered:
1.
Observe all clearances listed in vent clearances in these instruc-
tions.
2.
Termination should be positioned where vent vapors will not dam-
age plants or shrubs or air conditioning equipment.
3.
Termination should be located where it will not be affected by wind
gusts, light snow, airborne leaves or allow recirculation of flue
gases.
4.
Termination should be located where it will not be damaged or
exposed to flying stones, balls, etc.
5.
Termination should be positioned where vent vapors are not objec-
tionable.
6.
Horizontal portions of the vent system must slope upwards and be
supported to prevent sagging.
7.
Direct vent systems must be installed so the vent and the combus-
tion air pipes terminate in the same atmospheric zone. Refer to
Figures 36 or 37.
12" Min.
FIGURE 35: Termination Configuration - 1 Pipe
Condensation in Intake Pipe
Installations where the furnace and intake pipe are to be located in a
conditioned space and in a region that may have hot, humid weather
extending several consecutive days will have condensate form in the
intake pipe. Use of the supplied intake drain will ensure that any con-
densate will be safely diverted away from the internal components of
the furnace. Proper venting installation (of both intake and exhaust)
and sealing any equipment air leaks that might contact the intake pipe
will help reduce condensation.
Johnson Controls Unitary Products
Maintain 12" minimum clearance
above highest anticipated snow level.
Maximum 24" above roof.
12" Min.
12" vertical separation
between combustion air
Maintain 12" minimum
intake and vent.
clearance above
highest anticipated
snow level.
FIGURE 36: Termination Configuration - 2 Pipe
12" MIN.
12" MIN.
FIGURE 37: Termination Configuration - 2 Pipe Basement
VENTING MULTIPLE UNITS
Multiple units can be installed in a space or structure as either a single
pipe configuration or a two-pipe configuration.
The combustion air side of the single pipe configuration shown in Figure
42 is referred to in these instructions as ambient combustion air supply.
Follow the instructions for ambient combustion air installations, paying
particular attention to the section on air source from inside the building.
The vent for a single pipe system must be installed as specified in the
venting section of these instructions with both vents terminating as
shown in Figure 35. Each furnace must have a separate vent pipe.
Under NO circumstances can the two vent pipes be tied together.
The combustion air side of the two-pipe configuration shown in Figures
36 and 37 can be installed so the combustion air pipe terminates as
described in outdoor combustion air or ventilated combustion air sec-
tions in these instructions. Follow the instructions for outdoor combus-
tion air or ventilated combustion air and the instructions for installing the
vent system with the vent terminating as shown in Figure 38 or 39. The
two-pipe system must have a separate combustion air pipe and a sepa-
rate vent pipe for each furnace. Under NO circumstances can the two
combustion air or vent pipes be tied together. The combustion air and
vent pipes must terminate in the same atmospheric zone.
1083292-UIM-A-0114
12" minimum
below overhang
12" minimum
separation between
bottom of
combustion air pipe
and bottom of vent.
Maintain 12"
minimum clearance
above highest
anticipated snow
level or grade,
whichever is higher.
12" Minimum
below overhang
12" Minimum
separation between
bottom of
combustion air
intake and
bottom of vent
Maintain 12"
minimumclearance
above highest
anticipated snow
level or grade,
whichever is higher
31