INSTALLATION MANUAL
SINGLE STAGE ECM
RESIDENTIAL GAS FURNACES
MODELS: TL8E
(80% Upflow/Horizontal - Ultra Low NOx
Natural Gas Only)
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
ELECTRICAL POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
VENT SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . 13
Duct Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Furnace and Coil Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Horizontal Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Typical Attic Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Side Return Cutout Markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Cabinet and Duct Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Ratings & Physical / Electrical Data . . . . . . . . . . . . . . . . . . . . . . 8
Estimated Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
These high efficiency, compact units employ induced combustion, reli-
able hot surface ignition and high heat transfer tubular heat exchang-
ers. The units are factory shipped for installation in upflow or horizontal
applications.
These furnaces are designed for residential installation in a basement,
closet, alcove, attic, recreation room or garage and are also ideal for
commercial applications. All units are factory assembled, wired and
tested to assure safe dependable and economical installation and oper-
These units are Category I listed and may be common vented with
another gas appliance as allowed by the National Fuel Gas Code.
SECTION I: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
Johnson Controls Ducted Systems
LIST OF SECTIONS
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
OPERATION & DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . . . 19
REPLACEMENT PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . 21
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
LIST OF FIGURES
Furnace (STD-ECM) - Two Stage Air Conditioner . . . . . . . . . . . . . . 10
Combustion Air Inducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Casing to the Burner Compartment . . . . . . . . . . . . . . . . . . . . . . . . . 11
Outside and Ambient Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . 12
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Reading Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Furnace Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
LIST OF TABLES
Unconfined Space Minimum Area . . . . . . . . . . . . . . . . . . . . . . . 12
Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Gas Rate (CU FT/HR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
New: Nominal Manifold Pressure . . . . . . . . . . . . . . . . . . . . . . . 16
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or maintenance
can cause injury or property damage. Failure to carefully read and
follow all instructions in this manual can result in furnace mal-
function, death, personal injury and/or property damage. Only a
qualified contractor, installer or service agency should install this
product.
SPECIFIC SAFETY RULES AND PRECAUTIONS
1. Only Natural gas is approved for use with this furnace.
2. Install this furnace only in a location and position as specified in
these instructions.
3. A gas-fired furnace for installation in a residential garage must be
installed as specified in these instructions.
4. Provide adequate combustion and ventilation air to the furnace
space as specified in these instructions.
5. Combustion products must be discharged outdoors. Connect this
furnace to an approved vent system only, as specified in SECTION
VI of these instructions.
6. Test for gas leaks as specified in these instructions.
WARNING
!
5532522-UIM-B-0619

Advertisement

Table of Contents
loading

Summary of Contents for York TL8E

  • Page 1: Table Of Contents

    INSTALLATION MANUAL SINGLE STAGE ECM RESIDENTIAL GAS FURNACES MODELS: TL8E (80% Upflow/Horizontal - Ultra Low NOx Natural Gas Only) LIST OF SECTIONS SAFETY ......... . . 1 SAFETY CONTROLS .
  • Page 2: Combustion Air Quality

    5532522-UIM-B-0619 • Check the rating plate and power supply to be sure that the elec- WARNING trical characteristics match. All models use nominal 115 VAC, 1 Phase, 60 Hz power supply. DO NOT CONNECT THIS APPLI- ANCE TO A 50 Hz POWER SUPPLY OR A VOLTAGE ABOVE FIRE OR EXPLOSION HAZARD 130 VOLTS.
  • Page 3: Safety

    5532522-UIM-B-0619 CODES AND STANDARDS These instructions cover minimum requirements and conform to exist- ing national standards and safety codes. In some instances these Follow all national, local codes and standards in addition to this installa- instructions exceed certain local codes and ordinances, especially tion manual.
  • Page 4: Ductwork

    5532522-UIM-B-0619 SECTION II: DUCTWORK If a matching cased indoor coil is used, it may be placed directly on the furnace outlet and sealed to prevent leakage. If an uncased indoor coil DUCTWORK GENERAL INFORMATION with a thermoplastic drain pan is to be installed in the upflow/horizontal configuration, then extra 2”...
  • Page 5: Furnace And Coil Attachment

    5532522-UIM-B-0619 UPFLOW APPLICATION FURNACE COIL COIL RIGHT FLOW APPLICATION FURNACE COIL FURNACE LEFT FLOW APPLICATION NOTE: Verify that all drains are trapped or plugged. DRAIN PLUG FOR HORIZONTAL SECONDARY DRAIN DRAIN PLUG FOR VERTICAL SECONDARY DRAIN SECONDARY DRAIN PRIMARY DRAIN TRAP CONNECTION PRIMARY DRAIN TRAP CONNECTION...
  • Page 6: Typical Suspended Furnace / Crawl Space Installation

    5532522-UIM-B-0619 When moving or handling this furnace prior to installation, always leave the doors on the furnace to provide support and to prevent damage or warping of the cabinet. When lifting the furnace, support the ends of the furnace rather than lifting by the cabinet flanges at the return air open- ings (bottom or sides) or supply air opening.
  • Page 7: Filters

    5532522-UIM-B-0619 SECTION III: FILTERS IMPORTANT: Some accessories such as electronic air cleaners and FILTER INSTALLATION pleated media may require a larger side opening. Follow the instruc- tions supplied with that accessory for side opening requirements. Do CAUTION not cut the opening larger than the dimensions shown in Figure 6. HORIZONTAL FILTERS All filters and mounting provision must be field supplied.
  • Page 8: Electrical Power

    5532522-UIM-B-0619 GROUND UNION MANUAL SHUT-OFF DRIP VALVE MANUAL SHUT-OFF GROUND VALVE UNION GROUND UNION DRIP DRIP DRIP GROUND UNION UPFLOW FIGURE 9: Gas Piping HIGH ALTITUDE IMPORTANT: An accessible manual shutoff valve must be installed This furnace is constructed at the factory for natural gas-fired operation upstream of the furnace gas controls and within 6 feet (1.8 m) of the at 0 –...
  • Page 9: Electrical Wiring

    5532522-UIM-B-0619 SUPPLY VOLTAGE CONNECTIONS furnace. Route the furnace leads into the box using a protective bushing where the wires pass through the furnace panel. After making the wiring connections replace the wiring box cover and JUNCTION screws. Refer to Figure 10. 3.
  • Page 10: Thermostat Chart - Single Stage Hp With Single Stage Furnaces

    5532522-UIM-B-0619 FIGURE 12: Thermostat Chart - Single Stage HP with Single Stage Furnaces FIGURE 13: Thermostat Chart - 1H/2C - Single Stage Furnace (STD-ECM) - Two Stage Air Conditioner ACCESSORY CONNECTIONS HUMIDIFIER CONNECTION The furnace control will allow power-switching control of various acces- Two 1/4”...
  • Page 11: Vent System

    5532522-UIM-B-0619 TWINNING 2. This furnace must be vented into a fire clay tile lined masonry chim- ney only if a source of dilution air is provided, such as by common These furnaces are not to be twinned. If more than one furnace is venting with a draft hood equipped water heater.
  • Page 12: Estimated Free Area

    5532522-UIM-B-0619 Combustion Air Source From Outdoors WARNING The blocking effects of louvers, grilles and screens must be given con- sideration in calculating free area. If the free area of a specific louver or When a Category I furnace is removed or replaced, the original vent- grille is not known, refer to Table 5, to estimate free area.
  • Page 13: Start-Up And Adjustments

    5532522-UIM-B-0619 3. The duct shall be least the same cross-sectional area as the free Vent and Supply (Outside) Air Safety Check Procedure area of the air supply inlet opening to which it connects. For Category I furnaces, vent installations shall be in accordance with 4.
  • Page 14: Ation

    5532522-UIM-B-0619 GAS PIPING LEAK CHECK 3. System start-up will occur as follows: a. The induced draft blower will start and will run for several sec- WARNING onds in order to bring fresh combustion air into the combustion chamber. Then the induced draft blower will shut off and the hot surface igniter will glow for about 17 seconds.
  • Page 15: Gas Rate (Cu Ft/Hr)

    5532522-UIM-B-0619 Table 8: Gas Rate (CU FT/HR) Size of Test Dial Size of Test Dial Seconds For Seconds For 1 Revolution 1 Revolution 1 Cu Ft 2 Cu Ft 5 Cu Ft 1 Cu Ft 2 Cu Ft 5 Cu Ft 1800 1636 1500...
  • Page 16: Gas Valve

    5532522-UIM-B-0619 ADJUSTMENT OF MANIFOLD GAS PRESSURE & 3. Adjust manifold pressure by adjusting gas valve regulator screw for INPUT RATE the appropriate gas per the following: Table 10: New: Nominal Manifold Pressure Inlet and manifold gas pressure may be measured by connecting the “U”...
  • Page 17: Furnace Control Board

    5532522-UIM-B-0619 ADJUSTMENT OF TEMPERATURE RISE ADJUSTMENT OF FAN CONTROL SETTINGS This furnace is equipped with a time-on/time-off heating fan control. The DANGER fan on delay is fixed at 30 seconds. The fan off delay has 4 settings (A = 60 seconds, B = 90 seconds, C = 120 seconds, D = 180 seconds). The The temperature rise, or temperature difference between the return fan off delay is factory set to 120 seconds.
  • Page 18: Safety Controls

    5532522-UIM-B-0619 Table 11: Blower Performance CFM - Any Position (without filter) 1, 2 Airflow Data (SCFM) Models Speed Ext. Static Pressure (in. H2O) High 1363 1328 1282 1257 1211 1180 1145 1100 Medium High 1161 1128 1083 1045 060A12 Medium Medium Low High 1780...
  • Page 19: Operation & Diagnostics

    5532522-UIM-B-0619 SECTION IX: OPERATION & DIAGNOSTICS Hot Surface Ignition System WARNING SEQUENCE OF OPERATION The following describes the sequence of operation of the furnace. Refer to Owners Manual for component location. HOT SURFACE IGNITION SYSTEM Do not attempt to light this furnace by hand (with a match or any other Continuous Blower means).
  • Page 20 5532522-UIM-B-0619 gle call for heat, the control will also indicate 4 Red Flashes and will IGNITION CONTROL FLAME SENSE LEVELS enter a one-hour soft lockout. Normal flame sense current is approximately 5 RED FLASHES: Flame present with gas valve off. This fault indicates 3.7 microamps DC (μa) that the control board has sensed a flame during a period when the gas Low flame signal warning starts at 1.5 microamps.
  • Page 21: Replacement Parts List

    Click on the “Brand Links” button b. Click on the “Customer Service” button • You can contact us by mail. Just send a written request to: Johnson Controls Unitary Products Consumer Relations 5005 York Drive Norman, OK 73069 Johnson Controls Ducted Systems...
  • Page 22: Wiring Diagram

    5532522-UIM-B-0619 SECTION XI: WIRING DIAGRAM FIGURE 20: Wiring Diagram Johnson Controls Ducted Systems...
  • Page 23: Start Up Sheet

    5532522-UIM-B-0619 SECTION XII: START UP SHEET 33" 80% AFUE ECM Single Stage Ultra-Low NOx Gas Furnace Start Up Sheet Proper furnace start up is critical to customer comfort and equipment longevity Start-Up Date Technician Performing Start-Up Installing Contractor Name Owner Information Name Address City...
  • Page 24 Explain thermostat use and programming (if applicable) to owner Additional Job Detail Subject to change without notice. Published in U.S.A. 5532522-UIM-B-0619 Copyright © 2019 by Johnson Controls. All rights reserved. Supersedes: 5532522-UIM-A-1118 York International Corp. 5005 York Drive Norman, OK 73069...