Removing Existing Outdoor Unit; Positioning New Outdoor Unit - Lennox Elite Series XP13 Units Installation Instructions Manual

Elite xp13 series
Hide thumbs Also See for Elite Series XP13 Units:
Table of Contents

Advertisement

Removing Existing Outdoor Unit

Perform the following task at the existing outdoor unit:
S
Disconnect line set at the service valves.
S
Disconnect electrical service at the disconnect switch.
S
Remove old outdoor unit.

Positioning New Outdoor Unit

CAUTION
In order to avoid injury, take proper precaution when
lifting heavy objects.
See Unit Dimensions on page 3 for sizing mounting slab,
platforms or supports. Refer to figure 7 for mandatory
installation clearance requirements.
*
* SEE NOTES BELOW THIS FIGURE FOR FURTHER DETAILS.
Figure 7. Installation Clearances
NOTES:
S
Service clearance of 30 in. (762 mm) must be
maintained on one of the sides adjacent to the control
box.
S
Clearance to one of the other three sides must be 36
.
in. (914 mm)
S
Clearance to one of the remaining two sides may be
12 in. (305 mm) and the final side may be 6 in. (152
.
mm)
S
48 in. (1219 mm) clearance required on top of unit.
S
A clearance of 24 in. (610 mm) must be maintained
between two units.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
S
Some localities are adopting sound ordinances based
on the unit's sound level registered from the adjacent
506270−01 05/09
*
CONTROL PANEL
ACCESS LOCATION
*
*
property, not from the installation property. Install the
unit as far as possible from the property line.
S
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound
transmission. For proper placement of unit in relation
to a window see the provided illustration in figure 8.
INSTALL UNIT AWAY
FROM WINDOWS
TWO 90° ELBOWS INSTALLED
IN LINE SET WILL REDUCE
LINE SET VIBRATION.
Figure 8. Outside Unit Placement
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab
should be high enough above grade so that water from
higher ground will not collect around the unit. The slab
should have a slope tolerance as described in figure 9.
NOTE − If necessary for stability, anchor unit to slab as
described in Stabilizing Unit on Uneven Surfaces on page
7.
INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE TOLERANCE OF 2
DEGREES (OR 2 INCHES PER 5 FEET [50 MM PER 1.5 M]) AWAY FROM BUILDING
STRUCTURE.
GROUND LEVEL
Figure 9. Slab Mounting at Ground Level
Page 6
BUILDING
STRUCTURE
MOUNTING
SLAB

Advertisement

Table of Contents
loading

Table of Contents