Flushing The System - Lennox Elite Series XP13 Units Installation Instructions Manual

Elite xp13 series
Hide thumbs Also See for Elite Series XP13 Units:
Table of Contents

Advertisement

DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
DISTRIBUTOR
ASSEMBLY
VALVE STEM
VALVE STEM CAP
Figure 20. Typical Fixed Orifice Removal
TYPICAL TXV REMOVAL PROCEDURE
(Uncased Coil Shown)
TWO PIECE
PATCH PLATE
(UNCASED COIL
LIQUID LINE
ONLY)
ORIFICE HOUSING
DISTRIBUTOR
TUBES
DISTRIBUTOR
EQUALIZER
ASSEMBLY
LINE
MALE EQUALIZER LINE
FITTING
SENSING BULB
Figure 21. Typical TXV Removal
1. On fully cased coils, remove the coil access and
plumbing panels.
2. Remove any shipping clamps holding the liquid line
and distributor assembly.
3. Disconnect the equalizer line from the TXV equalizer
line fitting on the suction line.
4. Remove the suction line sensing bulb as illustrated in
figure 21.
506270−01 05/09
TEFLON RING
REMOVE AND DISCARD
VALVE STEM ASSEMBLY
FIXED
(IF PRESENT)
ORIFICE
BRASS NUT
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
(Uncased Coil Shown)
STUB END
TXV
TEFLON
RING
TEFLON
RING
SENSING
LIQUID LINE ASSEMBLY
WITH BRASS NUT
SUCTION
LINE
5. Disconnect the liquid line from the TXV at the liquid line
assembly.
6. Disconnect the TXV from the liquid line orifice housing.
Take care not to twist or damage distributor tubes
during this process.
7. Remove and discard TXV and the two Teflon rings as
illustrated in figure 21.
8. Use a field−provided fitting to temporary reconnect the
liquid line to the indoor unit's liquid line orifice housing.

Flushing the System

The line set and indoor unit coil must be flushed
with at least the same amount of clean refrigerant
that previously charged the system. Check the
charge in the flushing cylinder before proceeding.
This procedure should not be performed on
systems which contain contaminants (Example:
compressor burn out).
The
Environmental
prohibits the intentional venting of HFC refrigerants
during maintenance, service, repair and disposal of
LINE
appliance.
recycling or reclaiming must be followed.
If this unit is being matched with an approved line
set or indoor unit coil which was previously
charged with mineral oil, or if it is being matched
with a coil which was manufactured before
January of 1999, the coil and line set must be
flushed prior to installation. Take care to empty all
LIQUID
existing traps. Polyol ester (POE) oils are used in
LINE
Lennox units charged with HFC−410A refrigerant.
Residual mineral oil can act as an insulator,
preventing proper heat transfer. It can also clog
the expansion device, and reduce the system
performance and capacity.
Failure to properly flush the system per the
instructions below will void the warranty.
If the original system used:
S
HCFC−22 refrigerant, then flush the system using the
procedure provided in this section.
S
HFC−410A refrigerant, then proceed to Installing New
Refrigerant Metering Device.
Page 12
IMPORTANT
CAUTION
IMPORTANT
Protection
Approved
methods
IMPORTANT
Agency
(EPA)
of
recovery,

Advertisement

Table of Contents
loading

Table of Contents