Metering Devices and Flushing the System

FLUSHING
LINE SET AND INDOOR COIL (1 OF 2)
1
TYPICAL FIXED ORIFICE REMOVAL
PROCEDURE
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
DISTRIBUTOR
ASSEMBLY
REMOVE AND DISCARD
WHITE TEFLON SEAL (IF
PRESENT)
(Uncased Coil Shown)
A
On fully cased coils, remove the coil access and plumbing panels.
B
Remove any shipping clamps holding the liquid line and distributor
assembly.
C
Using two wrenches, disconnect liquid line from liquid line orifice
housing. Take care not to twist or damage distributor tubes during
this process.
D
Remove and discard fixed orifice, valve stem assembly if present
and Teflon washer as illustrated above.
E
Use a field−provided fitting to temporary reconnect the liquid line to
the indoor unit's liquid line orifice housing.
2
CONNECT GAUGES AND EQUIPMENT FOR
FLUSHING PROCEDURE
INVERTED CYLINDER
CONTAINS CLEAN TO
BE USED FOR
FLUSHING.
A
1
VAPOR LINE
SERVICE VALVE
EXISTING
INDOOR
B
UNIT
LIQUID LINE SERVICE
VALVE
RECOVERY
CYLINDER
D
A
Inverted cylinder with clean refrigerant to the vapor service valve.
B
gauge set (low side) to the liquid line valve.
C
gauge set center port to inlet on the recovery machine with an empty
recovery tank to the gauge set.
D
Connect recovery tank to recovery machines per machine
instructions.
506377−01 11/09
TEFLON RING
FIXED ORIFICE
BRASS NUT
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
GAUGE
MANIFOLD
LOW
NEW
OUTDOOR
UNIT
OPENED
CLOSED
TANK
RETURN
C
INLET
DISCHARGE
RECOVERY MACHINE
TYPICAL CHECK EXPANSION VALVE
REMOVAL AND REPLACEMENT PROCEDURE
TWO PIECE PATCH PLATE
LIQUID LINE
(UNCASED COIL ONLY)
DISTRIBUTOR
TUBES
OR
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER
LINE FITTING
SENSING BULB
A
On fully cased coils, remove the coil access and plumbing panels.
B
Remove any shipping clamps holding the liquid line and distributor as-
sembly.
C
Disconnect the equalizer line from the check expansion valve equaliz-
er line fitting on the vapor line.
D
Remove the vapor line sensing bulb.
E
Disconnect the liquid line from the check expansion valve at the liquid
line assembly.
F
Disconnect the check expansion valve from the liquid line orifice hous-
ing. Take care not to twist or damage distributor tubes during this pro-
cess.
G
Remove and discard check expansion valve and the two Teflon rings.
H
Use a field−provided fitting to temporary reconnect the liquid line to the
indoor unit's liquid line orifice housing.
I
Reverse above order to install.
HIGH
CAUTION
This procedure should not be performed on systems
which contain contaminants (Example compressor burn out.
3
FLUSHING LINE SET
The line set and indoor unit coil must be flushed with at least the
same amount of clean refrigerant that previously charged the sys-
tem. Check the charge in the flushing cylinder before proceeding.
B
A
Set the recovery machine for liquid recovery and start the recov-
ery machine. Open the gauge set valves to allow the recovery
machine to pull a vacuum on the existing system line set and in-
door unit coil.
B
Invert the cylinder of clean and open its valve to allow liquid re-
frigerant to flow into the system through the vapor line valve. Al-
low the refrigerant to pass from the cylinder and through the line
set and the indoor unit coil before it enters the recovery machine.
C
After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the vapor is
recovered. Allow the recovery machine to pull down to 0 the sys-
tem.
D
Close the valve on the inverted drum and the gauge set valves.
Pump the remaining refrigerant out of the recovery machine and
turn the machine off.
Page 10
(Uncased Coil Shown)
STUB END
CHECK
ORIFICE
EXPANSION
HOUSING
VALVE
TEFLON
RING
EQUALIZER
LINE
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
VAPOR
LINE
TEFLON
RING
SENSING
LINE
LIQUID
LINE