Electrical Data - Trane 7½ - 20 Tons Manual

Split system heat pumps
Table of Contents

Advertisement

Table 33.
Unit Wiring - Heat Pumps
Tons
Unit Model No.
TWA090A3
TWA090A4
TWA090AW
TWA120A3
10
TWA120A4
TWA120AW
TWA180B3
15
TWA180B4
TWA180BW
TWA240B3
20
TWA240B4
TWA240BW
(i)
HACR type circuit breaker per NEC.
Table 34.
Electrical Characteristics - Compressor and Condenser Fan Motors - 60 Cycle - Heat Pumps
Tons
Unit Model No.
TWA090A3
TWA090A4
TWA090AW
TWA120A3
10
TWA120A4
TWA120AW
TWA180B3
15
TWA180B4
TWA180BW
TWA240B3
20
TWA240B4
TWA240BW
32

Electrical Data

Unit Operating Voltage
Range
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632
Compressor Fan Motor
No.
Volts
Phase
(ea.)
1
208-230
3
1
460
3
1
575
3
1
208-230
3
1
460
3
1
575
3
2
208-230
3
2
460
3
2
575
3
2
208-230
3
2
460
3
2
575
3
Maximum Fuse Size or
Minimum Circuit
Ampacity
34.5
18.1
14.5
48.1
23.3
18.8
62.7
32.9
26.3
87.8
42.5
34.2
Amps
FLA
LRA
(ea.)
No.
25.1
182
1
13.2
94.9
1
10.6
70
1
33.7
278
1
16.5
124
1
13.4
92
1
25.1
182
2
13.2
94.9
2
10.6
70
2
33.7
278
2
16.5
124
2
13.4
92
2
Maximum Circuit
(i)
Breaker
50
25
20
70
35
25
80
45
35
100
50
45
Condenser Fan Motor
Amps
FLA
Volts
Phase
(ea.)
208-230
1
3.1
460
1
1.6
575
1
1.2
208-230
1
6
460
1
2.7
575
1
2
208-230
1
3.1
460
1
1.6
575
1
1.2
208-230
1
6
460
1
2.7
575
1
2
SSP-PRC001-EN
LRA
(ea.)
8.1
3.7
3
17
7
5.7
8.1
3.7
3
17
7
5.7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

5-20 tons

Table of Contents