Trane 7½ - 20 Tons Manual page 13

Split system heat pumps
Table of Contents

Advertisement

Performance Data
10 Tons Gross Cooling Capacities
Table 4.
Gross Cooling Capacities (MBh) 10 Ton TWA120A Heat Pump with 10 Ton TWE120A Air Handler
61
CFM Air
Ent
flow
DB °F
MBH
SHC
3600
75
114.6 90.1 126.2 76.3 138.8 51.1 110.6 88.1 121.8 74.5 134.0 49.4 106.2 85.9 117.1 72.6 128.9 47.7
80
115.0 104.8 126.4 85.8 138.8 66.4 111.1 102.8 122.0 83.9 134.0 64.6 106.9 100.7 117.3 81.9 128.9 62.6
85
117.1 117.1 126.5 100.7 138.8 81.2 113.7 113.7 122.0 98.6 134.0 79.3 110.1 110.1 117.4 96.5 129.0 77.4
90
122.7 122.7 126.9 115.2 138.9 95.9 119.2 119.2 122.7 113.2 134.2 94.0 115.5 115.5 118.2 111.1 129.1 92.1
4000
75
116.7 94.0 128.5 73.3 114.1 52.1 112.5 91.9 123.9 71.4 136.1 50.4 108.1 86.7 119.1 69.3 130.8 48.5
80
117.5 110.2 128.6 89.5 141.1 68.5 113.4 108.1 124.0 87.6 136.1 66.6 109.2 106.0 119.2 85.5 130.8 64.6
85
120.7 120.7 128.6 105.4 141.1 84.5 117.1 117.1 124.1 103.4 136.2 82.6 113.4 113.4 119.3 101.2 131.0 80.7
90
126.6 126.6 129.5 121.4 141.2 100.5 122.9 122.9 125.2 119.4 136.3 98.6 119.1 119.1 120.7 117.3 131.1 96.6
4400
75
118.5 97.7 130.3 75.5 142.9 53.0 114.2 95.6 125.6 73.6 137.8 51.1 109.6 93.4 120.7 71.6 132.4 49.2
80
119.7 115.3 130.4 93.0 142.9 70.4 115.6 113.2 125.8 91.0 137.8 68.5
85
123.9 123.9 130.5 110.0 143.0 87.7 120.2 120.2 125.9 107.9 138.0 85.8 116.3 116.3 121.1 105.8 132.6 83.8
90
129.9 129.9 131.9 127.4 143.1 104.8 126.1 126.1 127.5 125.4 138.1 102.9 122.2 122.2 122.0 122.0 132.7 100.9
4800
75
120.0 101.3 131.9 77.7 144.5 53.6 115.6 99.1 127.1 75.7 139.4 51.7 111.1 96.9 122.1 73.7 133.8 49.8
80
121.7 120.2 132.0 96.3 144.5 72.2 116.7 116.7 127.2 94.4 139.3 70.3 112.8 112.8 122.2 92.3 133.9 68.3
85
126.7 126.7 132.2 114.4 144.6 90.7 122.9 122.9 127.6 112.4 139.5 88.8 118.8 118.8 122.7 110.3 134.0 86.8
90
132.9 132.9 134.1 133.2 144.7 109.0 129.0 129.0 128.9 128.9 138.5 106.9 124.9 124.9 124.8 124.8 134.1 104.8
Ambient Temperature
61
CFM Air
Ent
flow
DB °F
MBH
SHC
3600
75
101.7 83.6 112.2 70.6 123.4 45.8
80
102.6 98.5 112.4 79.8 123.5 60.6
85
106.3 106.3 112.5 94.3 123.6 75.3
90
111.7 111.7 113.5 109.0 123.7 90.0
4000
75
103.5 87.5 114.0 67.2 125.2 46.5
80
104.9 103.8 114.2 83.4 125.3 62.6
85
109.5 109.5 114.4 99.0 125.4 78.6
90
115.0 115.0 115.9 115.2 125.5 94.5
4400
75
105.0 91.1 115.5 69.4 126.7 47.1
80
106.5 106.5 115.7 86.8 126.8 64.5
85
112.2 112.2 116.1 103.6 126.9 81.7
90
117.9 117.9 117.8 117.8 126.9 98.5
4800
75
106.3 94.7 116.7 71.5 128.0 47.7
80
108.7 108.7 116.9 89.8 128.0 66.2
85
114.6 114.6 117.6 108.0 128.2 84.7
90
120.5 120.5 120.4 120.4 128.2 102.6
Notes:
1. Dry coil condition. Total gross capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
2. All temperatures are in °F.
3. All capacities shown are gross and have not considered indoor fan heat.
4. To obtain net cooling capacities, subtract indoor fan heat.
5. MBH = Total Gross Cooling Capacity
6. SHC = Sensible Heat Capacity
SSP-PRC001-EN
85
67
73
MBH
SHC
MBH
SHC
MBH
115
Enter WB
67
73
MBH
SHC
MBH
SHC
Ambient Temperature
95
Entering WB
61
67
73
SHC
MBH
SHC
MBH
SHC
105
61
67
MBH
SHC
MBH
SHC
MBH
11.3 111.1 120.8 89.0 132.5 66.5
73
SHC
13