Table 19.
Evaporator Fan Performance 10 Tons TWE120A1, TWE120B1 - Air Handler
.10"
.20"
.30"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor and Field Supplied
3200
570 0.67 603 0.75 636 0.83 670 0.91 703 1.00 736 1.08 756 1.14 784 1.2 838 1.32 890 1.49 942 1.66
3400
560 0.71 592 0.79 623 0.88 652 0.95 685 1.04 716 1.12 743 1.18 762 1.24 790 1.3 844 1.43 895 1.59 948 1.8
3600 557 0.77 583 0.84 613 0.92 643 1.01 667 1.07 700 1.16 730 1.23 750 1.27 768 1.34 797 1.41 850 1.55 900 1.69 954 1.94
3800 579 0.94 605 1.01 634 1.09 663 1.18 683 1.24 710 1.29 738 1.37 762 1.42 785 1.49 813 1.56 861 1.72 911 1.87 —
4000 602 1.11 628 1.17 656 1.26 683 1.35 698 1.4 720 1.43 747 1.5 773 1.58 801 1.64 829 1.71 872 1.89 922 2.04 —
4200 626 1.23 651 1.31 677 1.4 703 1.48 714 1.53 741 1.59 765 1.66 790 1.72 815 1.81 841 1.9 888 2.08
4400 649 1.36 674 1.45 698 1.53 723 1.62 729 1.65 761 1.76 784 1.81 807 1.87 830 1.98 852 2.09 —
4600 669 1.52 692 1.62 714 1.69 735 1.77 747 1.82 782 1.92 798 1.99 815 2.06 —
4800 689 1.69 711 1.79 729 1.85 746 1.92 764 1.98 802 2.09 —
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Trane's factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.
(i)
Field Supplied Low Static Drive (use
Table 20.
Low Static Fan Drive 10 Tons TWE120A1, TWE120B1 - Air Handler
Motor Sheave Turns Open
0
1
2
3
4
5
(i)
Field supplied components required:
Blower Sheave: Fixed Pitch (8.8 inch Pitch Diameter)
Blower Sheave: 1.00 inch Bore, Single Groove, "A" Belt
Belt: A54
24
Evaporator Fan Performance, Low Static Fan Drive, 10 Tons
External Static Pressure (Inches of Water Gauge)
.40"
.50"
.60"
(i)
Low Static Drive
Table
20)
Nominal RPM
745
706
666
627
588
549
.70"
.80"
.90"
2 HP Standard Motor and Sheaves
(i)
Performance Data
1.00"
1.20"
1.40"
SSP-PRC001-EN
1.60"

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

5-20 tons