Positioning
Installation references
The boiler should be installed on a level surface which is substantial enough to carry
its weight.
It is recommended to place the boiler on a foundation or plinth. For dimensions see
the specification.
During the boiler installation observe all building regulations, the FeuVo and VDI 2050
[in Germany] and local regulations, particularly regarding the size of the boiler room,
the fresh air and exhaust air ventilation as well as the chimney stack connection.
Please note:
Only install the boiler in boiler rooms which are free from frost and where adequate
ventilation is ensured.
Drain the boiler, the DHW cylinder and the entire heating system if there is a danger of
frost, if the system has been shut down.
Position the boiler horizontally or slightly rising towards the back to ensure adequate
venting of any trapped air.
Boilers should not be installed in areas subject to aggressive vapours or very dusty/
highly humid conditions (workshops, washrooms, hobby rooms etc).
Please note:
The combustion air must be free from halogenated hydrocarbons (e.g. as contained
in sprays, solvents and cleaning fluids, paints and adhesives) and high dust
concentration.
Clearances towards walls and combustible materials must comply with local fire
regulations. The above clearances are recommended.
Keep the flue pipe connection as short as possible and inclined towards the chimney
stack.
Thoroughly seal-in the flue pipe.
Use flue pipe bends with clean-out covers to facilitate the cleaning of the flue pipe.
Repositioning the fixing screws enables the boiler door to be opened in the opposite
hand.