Connecting the Power Supply

Caution!
The separate protective earthing terminal provided on this product shall be permanently
!
connected to earth.
Notice!
Installation category (also called Overvoltage Category) specifies the level of mains voltage
surges that the equipment will be subjected to. The category depends upon the location of
the equipment, and on any external surge protection provided. Equipment in an industrial
environment, directly connected to major feeders/short branch circuits, is subjected to
Installation Category III. If this is the case, a reduction to Installation Category II is required.
This can be achieved by use of an isolating transformer with an earthed screen between
primary and secondary, or by fitting listed Surge Protective Devices (SPDs) from live to
neutral and from neutral to earth. Listed SPDs shall be designed for repeated limiting of
transient voltage surges, suitable rated for operating voltage and designated as follows:
- Type 2 (Permanently connected SPDs intended for installation on the load side of the
service equipment overcurrent device)
- Nominal Discharge Current (In) 20 kA min.
For example: FERRAZ SHAWMUT, STT2240SPG-CN, STT2BL240SPG-CN rated 120/240 VAC,
(In=20 kA)
The base with power supply box is available in three (3) power supply voltages (24 VAC,
120 VAC, or 230 VAC). To connect the power supply, follow these steps:
2013.11 | 5.2 | F.01U.291.981