Toshiba RAS-M10GDCV-E Service Manual page 26

Heat pump & cooling model
Hide thumbs Also See for RAS-M10GDCV-E:
Table of Contents

Advertisement

[External view]
The hanging bolt pitch on longitudinal direction is not divided at center with the ceiling opening size.
Therefore, check the relational position in the following figure.
1. Hanging down of indoor unit
Refer to installation figures of hanging material
and hanging bolt.
• Adjustment of hanging bolt length and nut
position
Adjust hanging bolt length and nut position as
shown in the figure below before hanging down
the indoor unit.
Considering pipe/wire connecting work inside the ceiling after the indoor unit has been hanged, select an installa-
tion place and determine piping direction.
• If the ceiling has been already set, lead refrigerant pipe, drain pipe, connecting wire, switch panel cord, etc. up
to the place where pipe and wire are connected before hanging the main unit.
REQUIREMENT
650 (Inside flange)
730 (Hanging bolt pich)
750
640 (Inside flange)
Fig. 9-3-3
15 to 20
NOTE :
Be sure to set the indoor unit horizontally so as not to
cause malfunction of the float switch (Option) or
leakage of water.
– 26 –
19.7
40
118
211
15
Hanging bolt
Nut with flange
(or washer and nut)
Square washer
20 to 30
Hexagonal nut
Fig. 9-3-4