Mitsubishi Electric Freqrol-A100 Instruction Manual page 131

Freqrol-a100 series transistorized inverter for variable torque loads
Table of Contents

Advertisement

Calibration procedure 2 (Example: Output current)
To output the output current or other item which is not easily allowed to reach 100% if operation is
performed, adjust the reference voltage output (when the set value of
Pr.
54
"FM-AM terminal
function selection" is "121"), then select any of the choices displayed.
1) Press the [SET] key in
....
The inverter is placed in the pa-
the PU operation mode.
rameter setting mode.
I
2) Type 54 and press the
....
The current set value in Pr. 54 is
[READ] key.
displayed.
-
-
-
' t l
-
3) Type 121 and press
........
The setting of reference voltage
I
the [WRITE] key.
output is complete.
I
I
1
2)
1
3)
4) Press the [SET] key.
.......
The inverter is put in the para-
5)
-
I
meter setting mode.
5) Type 901 and press
........
The current set value in Pr. 901
the [READ] key.
is displayed.
Type 60 and press the
.....
The setting of maximum running
[WRITE] key.
frequency is complete.
Sd
809pHz
1
7) Press the [FWD] key.
......
Forward operation is performed
at 60Hz. The motor need not be
connected for adjustment.
Display
8) Using the [A] or [ V ]
.......
Setting is complete.
key, adjust the voltage
across terminals AM-5
to 10V and press the
[WRITE] key.
......
When the output is loo%, the
output voltage is 10V. The
0
voltage is not stored unless
the [WRITE] key is pressed.
I
I
9) Press the [SET] key.
.......
The inverter is put in the parame-
ter setting mode.
. d
II
10) Type 54 and press the
....
The current set value in Pr. 54 is
[READ] key
.
displayed.
0
0
11) Type 102 and press the
...
The setting of output current is
'
I I
[ W R l T q key.
complete.
..The current value set in Pr.
56 "current monitoring refer-
e n c e " ~ l0O0/0 and the output
at this point is 10V.