Electrical Data - Outdoor Unit - Hp Without Powered Convenience Outlet; Electrical Data - Outdoor Unit - Hp With Powered Convenience Outlet - York R-410A Technical Manual

R-410a split-system air-cooled condensing units and air handlers predator series
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

Electrical Data - Outdoor Unit - HP Without Powered Convenience Outlet

Model
Power
Supply
208/230-3-60
PC090
460-3-60
575-3-60
208/230-3-60
PC120
460-3-60
575-3-60
208/230-3-60
PC180
460-3-60
575-3-60
208/230-3-60
PD180
460-3-60
575-3-60
208/230-3-60
PC240
460-3-60
575-3-60
208/230-3-60
PD240
460-3-60
575-3-60
1
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2
Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.

Electrical Data - Outdoor Unit - HP With Powered Convenience Outlet

Model
Power
Supply
208/230-3-60
PC090
460-3-60
575-3-60
208/230-3-60
PC120
460-3-60
575-3-60
208/230-3-60
PC180
460-3-60
575-3-60
208/230-3-60
PD180
460-3-60
575-3-60
208/230-3-60
PC240
460-3-60
575-3-60
208/230-3-60
PD240
460-3-60
575-3-60
1
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2
Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.
Johnson Controls Unitary Products
Compressors
RLA
MCC
Qty.
(each)
(each)
1
25.0
39
1
12.2
19
1
9.0
14
2
15.6
24
2
7.8
12
2
5.8
9
2
25.0
39
2
12.2
19
2
9.0
14
2
25.0
39
2
12.2
19
2
9.0
14
2
30.1
47
2
16.7
26
2
12.2
19
2
30.1
47
2
16.7
26
2
12.2
19
Compressors
RLA
MCC
Qty.
(each)
(each)
1
25.0
39
1
12.2
19
1
9.0
14
2
15.6
24
2
7.8
12
2
5.8
9
2
25.0
39
2
12.2
19
2
9.0
14
2
25.0
39
2
12.2
19
2
9.0
14
2
30.1
47
2
16.7
28
2
12.2
19
2
30.1
47
2
16.7
26
2
12.2
19
Outdoor Fan Motor
LRA
FLA
Qty
(each)
(each)
164
2
2.1
100
2
1.2
78
2
0.9
110
2
3.0
52
2
1.6
39
2
1.4
164
4
2.1
100
4
1.2
78
4
0.9
164
4
2.1
100
4
1.2
78
4
0.9
225
4
3.0
114
4
1.6
80
4
1.4
225
4
3.0
114
4
1.6
80
4
1.4
Outdoor Fan Motor
LRA
FLA
Qty
(each)
(each)
164
2
2.1
100
2
1.2
78
2
0.9
110
2
3.0
52
2
1.6
39
2
1.4
164
4
2.1
100
4
1.2
78
4
0.9
164
4
2.1
100
4
1.2
78
4
0.9
225
4
3.0
114
4
1.6
80
4
1.4
225
4
3.0
114
4
1.6
80
4
1.4
505428-YTG-C-0309
Pwr Conv
Minimum
Outlet
Circuit
1
Ampacity
FLA
0.0
35.5
0.0
17.6
0.0
13.1
0.0
41.2
0.0
20.8
0.0
15.8
0.0
64.7
0.0
32.2
0.0
24.0
0.0
64.7
0.0
32.2
0.0
24.0
0.0
79.8
0.0
44.0
0.0
32.9
0.0
79.8
0.0
44.0
0.0
32.9
Pwr Conv
Minimum
Outlet
Circuit
1
Ampacity
FLA
10.0
45.5
5.0
22.6
4.0
17.1
10.0
51.2
5.0
25.8
4.0
19.8
10.0
74.7
5.0
37.2
4.0
28.0
10.0
74.7
5.0
37.2
4.0
28.0
10.0
89.8
5.0
49.0
4.0
36.9
10.0
89.8
5.0
49.0
4.0
36.9
Maximum
Fuse Size
2
(A)
45
25
20
50
25
20
80
40
30
80
40
30
100
60
45
100
60
45
Maximum
Fuse Size
2
(A)
60
30
25
60
30
25
90
45
35
90
45
35
110
60
45
110
60
45
73