Vent Requirements; Vent Clearances; Altitude Considerations - Travis Industries 564 HO GS Installation Manual

Built-in direct vent fireplace natural gas or propane residential or mobile home
Hide thumbs Also See for 564 HO GS:
Table of Contents

Advertisement

18

Vent Requirements

The gas appliance and vent system must be vented directly to the outside of the building, and never
be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent
gas appliance must use its own separate vent system.
In addition to the requirements listed here, follow the requirements provided with the vent.
The fireplace must use the Travis Thimble (sku 250-02318) whenever the vent penetrates a wall.
Other penetrations only require a 1" (25mm) clearance and may use a standard firestop (make sure
the required 1" (25mm) clearance is met).

Vent Clearances

The vent must maintain the required clearance to combustible materials to prevent a fire. Do not fill
air spaces with insulation.
Sides
Above
Below
V ertical T ermination
Us e a roof flas hing and s torm collar
whenever pas s ing through the roof
Us e a fires top whenever
pas s ing through a ceiling
Us e a s upport box
on expos ed vent

Altitude Considerations

This heater has been tested at altitudes ranging from sea level to 6,000 feet (1800 M). In this testing we have
found that the heater, with its standard orifice, burns correctly with just an air shutter adjustment.
Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard.
Consult your dealer or installer if you suspect an improperly adjusted air shutter.
© Travis Industries
Installation
(
S ee C learances Above
for qualified installers only)
1" (25mm)
4" (102mm)
1" (25mm)
Required Thimble
4110505
Horizontal
T ermination
S ee C learances Above
S ee C learances Above
S ee C learances Above
100-01263_000