Valve Leak Test - Viessmann Vitocrossal 200 Installation Instructions Manual

Cm2 series 400, 500 and 620 gas condensing boiler with cylinder burner, heating input: 1445 to 2245 mbh (423 to 658 kw)
Hide thumbs Also See for Vitocrossal 200:
Table of Contents

Advertisement

Vitocrossal 200, CM2 400, 500 and 620 Installation
Gas Connections
Legend
A Manual test firing valve
B Gas Valve
C O-ring
D Gas valve flange
E Mounting nuts
F Nipple
G Elbow
H Nipple
I Manual gas shutoff valve
J Nipple (field supplied)
K Ground joint union (recommended) (field supplied)
WARNING
Escaped gas may lead to an explosion, which could
cause severe injuries or property damage.
(continued)
1. Refer to current CAN/CSA B149.1 and .2 or National
Fuel Gas Code ANSI Z223.1/NFPA 54, as well as
local codes for gas piping requirements and sizing.
Pipe size to the boiler must be determined based on:
-
pipe length
-
number of fittings
-
type of gas
-
maximum input requirements of all
gas appliances in the residence.
IMPORTANT
Design piping layout in such a way that piping does not
interfere with serviceable components.
2. Before connecting boiler to gas line, install ground
joint union, capped drip leg and a manual equipment
shutoff valve. Valves must be listed by a nationally
recognized testing agency. Make boiler gas connection
as shown.
3. Perform gas piping pressure test as described in the
following subsection.
IMPORTANT
Max. gas supply pressure: 14 "w.c.
4. Identify shutoff valves as such with a tab and
familiarize operator/ultimate owner of boiler with
these valves.
See Vitocrossal 200 CM2 Series 400 to 620
Service Instructions for applicable system
coding information.

Valve leak test

This is a test for checking the leakness tightness of the
valve and flange connections. It is recommended that
this test be included in the scheduled inspection and
maintenance procedures.
IMPORTANT
This test should only be performed by a trained licensed
heating contractor.
1. Close the manual test firing valve A.
2. Open the manual gas shutoff valve G.
3. Leak test all connections with a certified leak detector.
4. Close the manual gas shutoff valve G.
5. Open the manual test firing valve A.
6. Repair any leaks if necessary.
Boiler
31