MANTEL CLEARANCES

In addition to meeting noncombustible material clearances, you
must also meet required clearances between fireplace opening and
mantel shelf. If you do not meet the clearances listed below, you will
need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between mantel shelf and top of
fireplace opening, a hood is not required (see Figure 6).
Determining Minimum Mantel Clearance when
Using a Hood
If minimum clearances in Figure 6 are not met, you must have a
hood. When using a hood there are still certain minimum mantel
clearances required. Follow minimum clearances shown in Fig-
ure 7 when using a hood.
NOTICE: Surface temperatures of adjacent walls and
mantels become hot during operation. Walls and
mantels above the firebox may become hot to the
touch. If installed properly, these temperatures meet
the requirement of the national product standard.
Follow all minimum clearances shown in this manual.
NOTICE: If your installation does not meet the mini-
mum clearances shown, you must do one of the
following:
• operate the logs only with the flue damper open
• raise the mantel to an acceptable height
• remove the mantel
FLOOR CLEARANCES
A. If installing appliance on the floor level, you must maintain
the minimum distance of 14" to combustibles (see Figure 8).
B. If combustible materials are less than 14" to the fireplace, you
must install appliance at least 5" above the combustible floor-
ing (see Figure 9).
For more information, visit www.desatech.com
For more information, visit www.desatech.com
107068-01E
10"
8"
6"
1 /2
2
"
Minimum Non-
(A)
Combustible
Material
12"
8"
Minimum Non-
Combustible
Material Height
Figure 6 - Minimum Mantel Clearances Without Using Hood
12"
10"
8"
6"
1 /2
2
"
Minimum Non-
Combustible
Material
8"
Min.
Hood
(GA6050, GA6052,
(GA6050, GA6052)
or GA6053)
Figure 7 - Minimum Mantel Clearances When Using Hood
Combustible
Material
14"
Min.
Noncombustible Material
Figure 8 - Minimum Fireplace
Clearances If Installed at Floor
Level
INSTALLATION
Mantel Clearances
Floor Clearances
Mantel Shelf
Underside of
Mantel Shelf
All minimum
distances are
in inches
Log Set
18"
20"
22"
24"
24" Model
8"
14"
17"
20"
18" Model
Top of Fireplace
Opening
Distances to
Underside of
Mantel
Mantel Shelf
Underside of
Mantel Shelf
All minimum
distances are
in inches
12"
15"
18"
20"
Top of Fireplace
Opening
Distances to
Underside of
Mantel
Hearth
5"
Min.
Figure 9 - Minimum Fireplace
Clearances Above
Combustible Flooring
9 9
Log Set
18" and 24"
Models
Combustible
Material