Very Important Set-Up Instructions - Rheem AdvantagePlus HE55-100N Use & Care Manual

High efficiency commercial gas water heater
Table of Contents

Advertisement

4.
Horizontal lengths of exhaust vent must slope back
towards the water heater not less than ¼" per foot
to allow condensate to drain from the vent pipe. If
the exhaust pipe must be piped around an obstacle
that results in the creation of a low point, condensate
will collect in this low point and form a blockage. This
condensate must be drained away using a field-
installed condensate drain assembly as shown. (See
page 19)
5.
All piping must be fully supported. Use pipe hangers
at a minimum of 4 foot (1.2 m) intervals to prevent
sagging of the pipe where condensate may form.
6.
Do not use the water heater to support any piping.
7.
A screened straight coupling is provided with the water
heater for use as an outside exhaust termination.
G. VERY IMPORTANT SET-UP INSTRUCTIONS!
IF YOU HAVE A COMBUSTION ANALYZER, THE FOL-
LOWING RATINGS WILL BE VERY HELPFUL IN SET-
TING UP YOUR ADVANTAGEPLUS:
COMBUSTION SETTINGS
HIGH FIRING RATES AND LOW FIRING RATES ON
Natural Gas
low
Carbon
0–10
Monoxide
ppm
(CO%)
Carbon
8½% –
Dioxide
9½%
(CO2%)
BTU
100,000
130,000
199,000
15
ALL MODELS
Propane LP
high
low
0 ppm–
0–10
20 ppm
ppm
8½% –
9½% –
9½%
10½%
FAN SPEEDS
IGNITION
MIN
3000
2000
3000
2000
3000
2000
high
0 ppm–
20 ppm
9½% –
10½%
MAX
5400
6950
8500