Carrier 48AJ Operating And Service Manual page 113

Single package large rooftop units with scroll compressors and comfort link version 4.x controls
Table of Contents

Advertisement

POWER EXHAUST — The units can be equipped with an
optional power exhaust system. The power exhaust fans are
forward-curved fans with direct-drive motors. The motors are
controlled directly by the ComfortLink™ control through the
ECB1 board. On the 48/50A020-050 units there are 4 fans. On
the 48/50A051 and 060 units there are 6 fans. The fan sequenc-
es are controlled to provide 4 stages on the 48/50A020-050
units and 6 stages on the 48/50A051 and 060 units. There are
two control methods. For CV applications the fans can be
configured for 2 stages based on adjustable economizer
damper positions. For VAV applications and CV units with the
building pressure control option, the fans are sequenced to
maintain a building pressure set point based on a building
pressure transducer.
ECONOMIZER MOTOR — The economizer outside air and
return air dampers are gear-driven dampers without linkage. A
digitally controlled economizer motor controls their position.
The motor position is controlled by the ECB1 board by means
of a digital two-way communication signal. This allows for
accurate control of the motors as well as feedback information
and diagnostics information. The control has a self-calibration
routine that allows the motor position to be configured at initial
unit start-up. The motor is located on the economizer and can
be reached through the filter access door.
THERMISTORS AND PRESSURE TRANSDUCERS —
The unit is equipped with thermistors for measurement of
temperatures.
The units also have two pressure transducers that are con-
nected to the low side of the system. These two pressure trans-
ducers measure the low side pressure and are used for low pres-
sure protection and coil freeze protection.
By using the Saturated Condensing Temperature Sensors
and the low side pressure transducers, the ComfortLink control
displays the high and low side pressures and saturation temper-
atures and a normal gage set is not required.
SMOKE DETECTOR — The units can be equipped with an
optional smoke detector located in the return air. The detector
is wired to the ComfortLink controls and, if activated, will stop
the unit by means of a special fire mode. The smoke detector
can also be wired to an external alarm system through TB5
+
Fig. 27 — VFD Wiring
terminals 10 and 11. The sensor is located in the return air sec-
tion behind the filter access door.
FILTER STATUS SWITCH — The units can be equipped
with an optional filter status switch. The switch measures the
pressure drop across the filters and closes when an adjustable
pressure set point is exceeded. The sensor is located in the
return air section behind the filter access door.
RETURN AIR CO
SENSOR — The unit can also be
2
equipped with a return air IAQ CO
demand control ventilation. The sensor is located in the return
air section and can be accessed from the filter access door.
BOARD ADDRESSES — Each board in the system has an
address. The MBB has a default address of 1 but it does have
an instance jumper that should be set to 1 as shown in Fig. 22.
For the other boards in the system there is a 4-dip switch head-
er on each board that should be set as shown below.
BOARD
SW1
ECB1
0
ECB2
1
SCB
0
CEM
0
0 = On; 1 = Off
Table 112 — VFD Terminal Designations
TERMINAL
U1
V1
W1
Three-Phase Main Circuit Input Power Supply
U2
V2
Three-Phase AC Output to Motor, 0 V to
W2
Maximum Input Voltage Level
X1-11 (GND)
X1-12 (COMMON) Factory-supplied jumper
X1-10 (24 VDC)
X1-13 (DI-1)
Run (factory-supplied jumper)
X1-10 (24 VDC)
Start Enable 1 (factory-supplied jumper). When
X1-16 (DI-4)
opened the drive goes to emergency stop.
X1-2 (AI-1)
X1-3 (AGND)
Factory wired for 4 to 20 mA remote input
113
sensor that is used for the
2
SW2
SW3
SW4
0
0
0
0
0
0
0
0
0
0
0
0
FUNCTION
A48-7709

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents