Fig. 23 — Economizer Control Board (ECB1) and VAV Control Board (ECB2)
Table 107 — Economizer Control Board (ECB1) Inputs and Outputs
POINT
POINT DESCRIPTION
NAME
INPUTS
RMTIN
Remote occupancy
ECONENBL,
Economizer enable
ECOORIDE
RARH
Return air relative humidity
OARH
Outdoor air relative humidity
OUTPUTS
Economizer actuator
ECONOCMD
(analog control)
ECONOCMD Economizer actuator
(digital control)
PE_A
Power Exhaust stage A
PE_B
Power Exhaust stage B
PE_C
Power Exhaust stage C
ECON_PWR
Economizer Power
I/O POINT
PLUG AND PIN
NAME
REFERENCE
DI1
J4, 1-2
DI2
J4, 3-4
AN1
J5, 1-3
AN2
J5, 4-6
AO1
J9, 1-2
PP/MP
J7, 1-3
RLY1
J8, 1-3
RLY 2
J8, 4-6
RLY 3
J8, 7-9
RLY 6
J8, 16-18
109
SIGNAL PIN(S)
2
4
1=24VDC, 2=0-20mA in, 3=GND
4=24VDC, 5=0-20mA in, 6=GND
1=0-20mA, 2=GND
1=PP/MP Data, 2=24VAC, 3=GND
1 = 2 = RLY1A, 3 = RLY1B
4 =5 = RLY2A, 6 = RLY2B
7 = 8 = RLY3A, 9 = RLY3B
16 = 17 = RLY6A, 18 = RLY6B
A48-7706
PORT STATE
24VAC = 1, 0VAC = 0
24VAC = 1, 0VAC = 0
0-20mA
0-20mA
0-20mA OUT
Belimo PP/MP Protocol
1 = Closes RLY1A/RLY1B
1 = Closes RLY2A/RLY2B
1 = Closes RLY3A/RLY3B
1 = Closes RLY6A/RLY6B