Indoor Expansion Device - York YHJF60 Installation Manual

R-410a outdoor split-system heat pump 14.5 seer 5 tons – 1 phase
Hide thumbs Also See for YHJF60:
Table of Contents

Advertisement

Do not connect manifold gauges unless trouble is suspected. Approx-
imately 3/4 ounce of refrigerant will be lost each time a standard man-
ifold gauge is connected.
10.Release the refrigerant charge into the system in accordance with
the SYSTEM CHARGE procedures. Open the liquid line base valve
first and let pressures equalize. Then, open the suction line base
valve. When opening either valve, use an appropriate hex head
wrench and back seat the base valve by turning it counter clockwise
until it stops against the chamfered retaining wall, and then turn it
back 1/8 turn. If the service valve is a ball valve, use an adjustable
end wrench to turn valve stem one-quarter turn counterclockwise to
open. Do not overturn (or the valve stem may break or become dam-
aged).
11.To prevent leaks, replace base valve caps finger tight, and then
tighten the cap an additional 1/12 turn (1/2 hex flat).
12.Replace cap on service ports. Do not remove the flare caps from the
service ports except when necessary for servicing the system.
13. See "System Charge" section for checking and recording system
charge.
SECTION IV: INDOOR EXPANSION DEVICE
THERMOSTATIC EXPANSION VALVE (TXV) INSTAL-
LATION
Before accomplishing the following procedures, verify the proper TXV
kit to be installed on the coil. Refer to supplied Tabular Data Sheet for
specific TXV kit and indoor coil match up.
The following are basic steps for installation of a TXV kit. For detailed
instructions, refer to the Installation Instructions accompanying the TXV
kit.
Install TXV kit as follows:
1. Relieve nitrogen holding charge by depressing the Schrader valve
stem located in the end of the suction line. After nitrogen holding
charge is completely discharged, cut off the spundown copper end of
the suction line to allow installation of the field supplied suction line.
In all cases, do not mount the TXV bulb until after the suction line is
brazed and has had sufficient time to cool.
Dry nitrogen should always be supplied through the tubing while it is
being brazed, because the temperature is high enough to cause oxi-
dation of the copper unless an inert atmosphere is provided. The flow
of dry nitrogen should continue until the joint has cooled. Always use
a pressure regulator and safety valve to insure that only low pressure
dry nitrogen is introduced into the tubing. Only a small flow is neces-
sary to displace air and prevent oxidation.
2. Slide indoor coil out of cabinet far enough to gain access to equal-
izer fitting on the suction line.
NOTICE
All connections to be brazed are copper-to-copper and should be
brazed with a phosphorous-copper alloy material such as Silfos-5 or
equivalent. Soft solder is NOT to be used.
Johnson Controls Unitary Products
3. Before the suction line from the outdoor unit is brazed to the indoor
coil suction line, remove and discard black plastic cap from equalizer
fitting on the indoor coil suction line.
4. Loosen and remove distributor cap seal.
NOTICE
Do not install TXV onto distributor assembly until field supplied liquid
line is brazed onto the indoor coil liquid line and cooled.
5. Install the TXV to the distributor assembly by hand tightening, and
then turn fitting an additional 1/4 turn to seal. Do not overtighten fit-
tings.
Do not use slip joint pliers. Damage and distortion of distributor can
prevent proper seal. Use appropriate sized adjustable end wrench.
6. Install the liquid line to the top of the TXV using the liquid line fitting
which is supplied with the indoor coil. Hand modify the liquid line to
align with casing opening. Hand tighten the liquid line on the TXV,
and tighten an additional 1/4 turn to seal.
A schrader valve core MUST NOT be installed in the equalizer fitting
when the TXV kit is installed. Poor system performance or system
failure could result.
NOTICE
Do not install TXV equalizer line onto equalizer fitting nor the TVX
bulb onto the suction vapor line until field supplied suction line is
brazed onto the indoor coil suction line and cooled.
7. Install the TXV equalizer line onto the equalizer fitting of the suction
line. Hand tighten the 1/4" SAE nut to the equalizer fitting, and
tighten an additional 1/3 turn to seal.
NOTICE
The TXV bulb is to be installed on the suction line near the equalizer
line, using the two bulb clamps furnished with the TXV assembly kit.
The bulb is to make maximum contact. The TXV installation instruc-
tion provide an illustration of proper bulb location.
8. Install the TXV bulb to the suction line near the equalizer line, using
the bulb clamp(s) furnished with the TXV assembly kit. Ensure the
bulb is making maximum contact.
a.
Install the bulb on the suction line near the equalizer line with
the bulb horizontal to the suction line. On a suction line under
7/8" Outside Diameter (O.D.), install the bulb on top of the
line. On a suction line 7/8" O.D. or larger, install the bulb at
about the 2 or 10 o'clock position.
b.
If bulb must be installed vertically to the suction line, position
the bulb at least 16 inches (40.6 cm) from any bend and on
the opposite side of the bend plane. Positioned the bulb with
the bulb tail at the top, so that the bulb acts as a reservoir.
c.
Use thermal insulation provided to protect the bulb from the
effect of the surrounding ambient temperature. Cover the
bulb completely to insulate from air-stream.
9. Slide indoor coil back into cabinet.
10.Leak test system after outdoor unit is connected.
835959-UIM-D-0814