Gas Piping - Carrier 58RAV Installation, Start-Up, And Operating Instructions Manual

Downflow/horizontal induced-combustion furnaces
Hide thumbs Also See for 58RAV:
Table of Contents

Advertisement

Fig. 8 and Table 4 for horizontal applications. Horizontal filter
retainers must be field supplied. See Fig. 9 for downflow applica-
tions.
AIRFLOW
12"
FIELD-SUPPLIED
FILTER RETAINERS
Fig. 8—Horizontal Filter Arrangement
Table 4—Filter Retainer (In.)
FURNACE
CASING WIDTH
AND QUANTITY
14-3/16
(2) 14 X 20 X 1
17-1/2
(2) 14 X 20 X 1
21
(2) 16 X 20 X 1
24-1/2
(2) 16 X 20 X 1
INSTALLATION
POSITION
OF FILTERS
RETURN-AIR
PLENUM
ACCESS DOOR
Fig. 9—Downflow Filter Arrangement
Step 7—Gas Piping
Gas piping must be installed in accordance with national and local
codes. Refer to the current edition of the NFGC.
D
4"
A82173
FILTER SIZE
D
14-3/8
13-3/8
11-5/8
10-1/4
AIRFLOW
A88486
Canadian installations must be installed in accordance with NSC-
NGPIC and all authorities having jurisdiction.
Refer to Table 5 for recommended gas pipe sizing. Risers should
be used to connect to the furnace and to the meter.
Table 5—Maximum Capacity of Pipe *
NOMINAL IRON
INTERNAL
PIPE SIZE
DIAMETER
(IN.)
(IN.)
1/2
0.622
3/4
0.824
1
1.049
1-1/4
1.380
1-1/2
1.610
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a
pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table
10-2 NFPA 54/ANSI Z223.1-1992.
If a flexible connector is required or allowed by the authority
having jurisdiction, black iron pipe shall be installed at the
gas valve and extend a minimum of 2 in. outside the furnace
casing.
Use the proper length of pipes to avoid stress on the gas
control manifold. Failure to follow this warning could result
in a gas leak, causing fire, explosion, personal injury, or
death.
Connect the gas pipe to the furnace using a backup wrench to
avoid damaging gas controls.
Never purge a line into a combustion chamber. Never use
matches, candles, flame, or other sources of ignition to check
for gas leakage. Use a soap-and-water solution to check for
gas leaks. Failure to follow this warning could result in fire,
explosion, personal injury, or death.
Joint compounds (pipe dope) should be applied sparingly and only
to the male threads of the joints. This pipe dope must be resistant
to the action of propane gas.
Install an accessible manual shut-off valve upstream of the furnace
gas controls and within 72 in. of the furnace. A 1/8-in. NPT
plugged tapping, accessible for test gage connection, must be
installed immediately upstream of the gas supply connection to the
furnace and downstream of the manual shut-off valve. Place a
ground joint union between the gas control manifold and the
manual shut-off.
Install a sediment trap in the riser leading to the furnace. The trap
can be installed by connecting a tee to the riser leading from the
furnace. Connect a capped nipple into the lower end of the tee. The
capped nipple should extend below the level of the gas controls.
(See Fig. 10.)
Piping should be pressure tested in accordance with local and
national plumbing and gas codes before the furnace has been
attached. If the pressure exceeds 0.5 psig (14-in. wc), the gas
supply pipe must be disconnected from the furnace and capped
before the pressure test. If the test pressure is equal to or less than
7
LENGTH OF PIPE (FT)
10
20
30
40
50
175
120
97
82
73
360
250
200
170 151
680
465
375
320 285
1400
950
770
660 580
2100 1460 1180 990 900

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents