System Design
● Cooling
40
30
24
20
13.5
10
(ºCWB)
-20
● Heating
40
31
30
20
10
10
-21
(ºCDB)
-30
Note 1 : The remote control temperature setting range is as shown in the table below. This is slightly
different from the system operating temperature range.
Cooling
Heating
Note 2 : When heating starts (during warm-up), the system can operate even if the indoor temperature is
below 10ºC.
-10
5
-10
0
Outdoor intake air dry bulb temperature (ºCDB)
Operating range for
heating
-20
-10
Outdoor intake air wet bulb temperature (ºCWB)
Upper limit
30
26
2. Operating temperature ranges
for heating and cooling
Standard Specification
With added gas shut-off
valve (sold separately)
Operating range for cooling
Indoor relative humidity
45-85%
10
20
15.5
0
10
Lower limit
18
16
D-5
43
30
40
20
30
50
40