Separately Sold Parts
Cautions regarding installation work
• Cautions regarding connecting the KP pipe
1) When connecting the KP pipe, sufficiently insert the top until the warning mark (red line) on the
male connector side becomes hidden. A clicking sound will be heard when the top is connected
properly. Refer to Figure 6.
2) Never cut the KP pipe. If size adjustment is necessary, use a slide pipe.
3) For other points regarding the KP pipe, follow the instructions provided by the manufacturer.
• Method of securing the exhaust pipe
1) To secure the exhaust pipe, attach the fittings (support legs and split halves) on site, and use the
bolts/screws of the unit top plate to secure the pipe. Refer to the example in Figure 7.
2) Secure the exhaust gas pipe extending from the main body of the unit to an external wall or the
like using the fittings every 1.5 to 2.0 m.
3) The length from the exhaust extension pipe final securing edge is limited to 500 mm or less. Refer
to Figure 7.
• Separation distance of the exhaust pipe
The separation distance (mm) of the exhaust pipe from building parts finished with combustible
material, flame retardant material, or quasi-noncombustible material shall be as shown in Figure 8.
1. Outdoor unit related parts
F-4
Figure 7
Figure 8 (Space part)