GEM KMG Series Installation And Maintenance Manual page 23

Combination oven with direct steam and with steam generator
Table of Contents

Advertisement

12 • OPERATING AT THE RATED HEAT OUTPUT
Check the combustion, CO (ppm) and CO2
(%) values, with an appropriate instrument.
Start the oven working, with the door open,
and wait for approximately 5 minutes.
Position the flue gas collection probe in the
flue gas outlet pipe (chamber and boiler).
The CO
must be for:
2
Natural gas between 9% and 10.5%
L.P.G.
between 9% and 13%
Conversion: As mentioned above, every appliance is factory set to burn the type of gas specified,
it may become necessary nonetheless to convert the appliance from one type of gas to another.
Therefore, only personnel authorized by the company and belonging to the technical service who
have the corresponding technical handbook can do this work.
The CO must be no greater than 300 ppm
(measured).
I f these readings are outside the ranges,
proceed as stated in the technical manual.
F or the conversion from natural gas to LPG,
or vice versa, proceed as described in the
technical manual.
- Boiler Burner
Repeat these operations, setting 130°C steam
cooking (also with door closed).
23
90027360rev00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents