Using The 4-Pin Mini-Phoenix Connector For Data With External Power - AMX NetLinx NI-2100 Hardware Reference Manual

Netlinx integrated controllers
Hide thumbs Also See for NetLinx NI-2100:
Table of Contents

Advertisement

Connections and Wiring

Using the 4-pin Mini-Phoenix Connector For Data With External Power

To use the 4-pin 3.5 mm mini-Phoenix (female) captive-wire connector for data communication and power
transfer, the incoming PWR and GND cable from the 12 VDC-compliant power supply must be connected to
the AXlink cable connector going to the Integrated Controller. FIG. 11 shows the wiring diagram. Always use
a local power supply to power the Integrated Controller unit.
To the Integrated Controller's
AXlink/PWR connector
Top view
FIG. 11
4-pin mini-Phoenix connector wiring diagram (using external power source)
When you connect an external power supply, do not connect the wire from the PWR
terminal (coming from the external device) to the PWR terminal on the Phoenix
connector attached to the Controller unit. Make sure to connect only the AXM, AXP,
and GND wires to the Controller's Phoenix connector when using an external power
supply.
Make sure to connect only the GND wire on the AXlink/PWR connector when using a separate 12 VDC
power supply. Do not connect the PWR wire to the AXlink connector's PWR (+) opening.
24
Local +12 VDC
PWR (+)
power supply
(coming from
GND (-)
an external
power supply)
NI-2100, NI-3100, NI-4100 Hardware Reference Guide
To the external AXlink device
Top view

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netlinx ni-3100Netlinx ni-4100

Table of Contents