Duct Connections - Trane UD1A040A9241A Series Installer's Manual

Upflow / horizontal — downflow / horizontal, gas-fired furnaces, “fan assisted combustion system
Table of Contents

Advertisement

Installer's Guide
TABLE 3
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
Furnace
Maximum
Air From
BTUH/INPUT
Inside
Rating
40,000
100
60,000
100
80,000
100
100,000
100
120,000
120
140,000
140
9
0
8
Air From Outside
Vertical
Horizontal
Duct
Duct
10
20
15
30
20
40
25
50
30
60
35
70

DUCT CONNECTIONS

Air duct systems should be installed in accordance with
standards for air conditioning systems, National Fire
Protection Association Pamphlet No. 90. They should be
sized in accordance with ACCA Manual D or whichever is
applicable. Check controls to make certain they are correct
for the electrical supply.
Central furnaces, when used in connection with cooling units,
shall be installed in parallel or on the upstream side of the
cooling units to avoid condensation in the heating element,
unless the furnace has been specifically approved for down-
stream installation. With a parallel flow arrangement, the
dampers or other means used to control flow of air shall be
adequate to prevent chilled air from entering the furnace, and
if manually operated, must be equipped with means to
prevent operation of either unit unless the damper is in full
heat or cool position.
On any job, flexible connections of nonflammable material
may be used for return air and discharge connections to
prevent transmission of vibration. Though these units
have been specifically designed for quiet, vibration free
operation, air ducts can act as sounding boards and could,
if poorly installed, amplify the slightest vibration to the
annoyance level.
When the furnace is located in a utility room adjacent to the
living area, the system should be carefully designed with
returns which minimize noise transmission through the
return air grille. Although these winter air conditioners are
designed with large blowers operating at moderate speeds,
any blower moving a high volume of air will produce audible
noise which could be objectionable when the unit is located
very close to a living area. It is often advisable to route the
return air ducts under the floor or through the attic. Such
design permits the installation of air return remote from the
living area (i.e. central hall).
When the furnace is installed so that the supply ducts carry
air circulated by the furnace to areas outside the space
containing the furnace, the return air shall also be handled
by a duct(s) sealed to the furnace and terminating outside
the space containing the furnace.
Minimum return air "entering temperature" for the
furnace is 55° F.
Where there is no complete return duct system, the return
connection must be run full size from the furnace to a location
outside the utility room, basement, attic, or crawl space.
DO NOT install return air through the back of the
furnace cabinet.
RETURN AIR DUCT CONNECTION
NOTE:
On upflow 5 or 6 ton airflow models where the airflow
requirement exceeds 1800 CFM - Models will require
return air openings and filters on: (1) both sides; or (2)
one side and the bottom; or (3) just the bottom.
All return air duct systems should provide for installation of
return air filters.
1. Determine the appropriate position to set the furnace in
order to connect to the existing supply and return
ductwork.
2. For side return installations on upflow models, remove
the insulation around the opening in the blower
compartment.
18-CD19D7-22

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents