High Altitude Derate - Trane UD1A040A9241A Series Installer's Manual

Upflow / horizontal — downflow / horizontal, gas-fired furnaces, “fan assisted combustion system
Table of Contents

Advertisement

TABLE 12
ORIFICE SIZES
INPUT
NUMBER
RATING
OF
BTUH
BURNERS
40,000
2
60,000
3
80,000
4
100,000
5
120,000
6
140,000
7
TABLE 13
PART NUMBERS FOR REPLACEMENT ORIFICES
DRILL
PART
SIZE
NUMBER
44
ORF00501
45
ORF00644
46
ORF00909
47
ORF00910
48
ORF01099
49
ORF00503
50
ORF00493

HIGH ALTITUDE DERATE

Input ratings (BTUH) of these furnaces are based on sea
level operation and should not be changed at elevations up to
2,000 ft.
If the installation is 2,000 ft. or above, the furnace input rate
(BTUH) shall be reduced 4% for each 1,000 ft. above sea
level. The furnace input rate shall be checked by clocking
the gas flow rate (CFH) and multiplying by the heating value
obtained from the local utility supplier for the gas being
delivered at the installed altitude. Input rate changes can be
made by adjusting the manifold pressure (min 3.0 - max
3.7 in. W.C. - Natural Gas) or changing orifices (orifice
change may not always be required). If the desired input rate
cannot be achieved with a change in manifold pressure, then
the orifices must be changed. LP installations will require an
orifice change.
IMPORTANT: Reinstall the propane orifices to the same depth
as the orifices supplied with the equipment.
See Table 15 (page 20) for help in selecting orifices if orifice
change is required. Furnace input rate and temperature rise
should be checked again after changing orifices to confirm
the proper rate for the altitude.
Installations above 4,000 feet may require a pressure switch
change. If required, use the BAYHALT*** Kit (High Altitude
Accessory Kit) listed in PRODUCT DATA.
Installation of this furnace at altitudes above 2,000 ft.
(610m) shall be in accordance with the local codes, or in the
absence of local codes, the National Fuel Gas Code, ANSI
Z223.1/ NFPA 54 or National Standard of Canada, Natural
Gas and Propane Installation Code, CSA 149.1. Installation of
this furnace at altitudes above 2,000 ft. (610m) shall be made
in accordance with the listed high Altitude Conversion Kit
available with this furnace.
18-CD19D7-22
MAIN BURNER ORIFICE
DRILL SIZE
NAT. GAS
LP GAS
45
56
45
56
45
56
45
56
45
56
45
56
DRILL
PART
SIZE
NUMBER
54
ORF00555
55
ORF00693
56
ORF00907
57
ORF00908
58
ORF01338
59
ORF01339
Installer's Guide
TABLE 14
GAS FLOW IN CUBIC FEET PER HOUR
2 CUBIC FOOT DIAL
SEC. FLOW SEC. FLOW SEC. FLOW SEC. FLOW
8
900
29
248
9
800
30
240
10
720
31
232
11
655
32
225
12
600
33
218
13
555
34
212
14
514
35
206
15
480
36
200
16
450
37
195
17
424
38
189
18
400
39
185
19
379
40
180
20
360
41
176
21
343
42
172
22
327
43
167
23
313
44
164
24
300
45
160
25
288
46
157
26
277
47
153
27
267
48
150
28
257
49
147
Outlet Pressure Boss
Outlet Pressure Boss
j
Inlet Pressure
let Pressure
Boss (opt.) .)
Boss
On/Off ff Swi
White-Rodgers 36G gas valve
k
Outlet Pressure Boss
Inlet Pressure
Boss (opt.)
On/Off Switch
White-Rodgers 36J gas valve
50
144
82
88
51
141
84
86
52
138
86
84
53
136
88
82
54
133
90
80
55
131
92
78
56
129
94
76
57
126
96
75
58
124
98
73
59
122
100
72
60
120
104
69
62
116
108
67
64
112
112
64
66
109
116
62
68
106
120
60
70
103
124
58
72
100
128
56
74
97
132
54
76
95
136
53
78
92
140
51
80
90
144
50
Regul ulator
tor
Adjust
Adj
ust
Switch ch
Regulator
Adjustment
19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents