Lev Time Chart - Mitsubishi Electric MSH-18RV Service Manual

Split-type, heat pump air conditioners
Table of Contents

Advertisement

2 When the temperature difference
RT13 in the indoor unit is 2: or more for a fixed time at cool or dry operation, the target discharge temperature is
changed. After the temperature is changed, when temperature difference
is changed again. The LEV opening is controlled based on the changed target discharge temperature and the temper-
ature difference
RT.
Ta (:)
more than Tb+10
Tb+5 to Tb+10
Tb+2 to Tb+5
Tb-2 to Tb+2
Tb-5 to Tb-2
Tb-10 to Tb-5
less than Tb-10
NOTE : Discharge temperature : Ta, Target discharge temperature : Tb
The target discharge temperature (Tb) is set according to the operation mode or the unit status as follows.
HEAT
COOL (Normal)
COOL (
RT is less than 2:, or
COOL (
RT is 3 :or more.)
NOTE : Target discharge temperature : Tb
NOTE : When the discharge temperature (Ta) is 50: or less on the cool operation, or is 49: or less on heat operation,
LEV opening is set in 54 pulse.
When this state continues for 20 minutes, the compressor is stopped and restarts in 3 minutes.
When the compressor is stopped, the indoor unit indicates the abnormality of refrigerant system and stops.
(OPERATION INDICATOR lamp is 10-time flashing on and off.)

(2) LEV time chart

Opening
Power ON
completely
Remote
controller
ON
Standard opening
Initial opening
Positioning
NOTE : Opening increases and decreases to be in the target discharge temperature during operation.
RT between indoor coil thermistor (main) RT12 and indoor coil thermistor (sub)
less than 2:
20
10
2
0
-2
-5
-10
Operation mode
RT is 2:or more and less than 3:.)
Thermostat
Operation
OFF
Standard opening
Thermostat
ON
Initial opening
Opening in stop
RT is 3: or more, the target temperature
RT
2: or more and less than 3:
60
20
2
0
-2
-5
-10
Opening
Remote
completely
controller
Operation
OFF
Opening in stop
49
3: or more
60
20
2
0
-2
-5
-10
Tb (:)
93
93
75
65
Remote
controller
ON
Operation
Standard opening
Initial opening
Positioning
Time