Rear View - York SUNLINE MagnaDRY DR 180 Submittal Data Sheet

Gas/electric single package air conditioners
Hide thumbs Also See for SUNLINE MagnaDRY DR 180:

Advertisement

258463-YSD-E-0508
Dimensions listed are for side
duct flange openings; see
Field Accessories for Side
Duct Flange Kit.
LOCATION
Front
Rear
Left Side (Filter Access)
Right Side (Cond. Coil)
1
Below Unit
2
Above Unit
1. Units may be installed on combustible floors made from wood or
class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging structures or
shrubs should not obstruct condenser air discharge outlet.
3. If economizer is factory installed, the unassembled rain hood
must be removed from its ride along position in front of evapora-
tor coil, or in the outdoor air compartment, prior to final installa-
tion.
Johnson Controls Unitary Products
40-3/8"
SUPPLY
AIR
COMPRESSOR
ACCESS
SUPPLY AIR
18-5/8"
ACCESS
5-1/8"
RETURN AIR
ACCESS
REAR
VIEW
CLEARANCE
36"
24" (Less Economizer)
49" (With Economizer)
24" (Less Economizer)
3
36" (With Economizer)
36"
0"
72" With 36" Maximum
Horizontal Overhang (For
Condenser Air Discharge)
RETURN
AIR
OUTDOOR
AIR
27-3/4"
39-5/8"
NOTE: ELEC / ELEC Models: Units and ductwork are
approved for zero clearance to combustible material
when equipped with electric heaters.
GAS / ELEC Models: A 1" clearance must be provided
between any combustible material and the supply air
ductwork for a distance of 3 feet from the unit.
The products of combustion must not be allowed to
accumulate within a confined space and recirculate.
Locate unit so that the vent air outlet hood is at least:
• Three (3) feet above any force air inlet located within
10 horizontal feet (excluding those integral to the
unit).
• Four (4) feet below, four horizontal feet from, or one
foot above any door or gravity air inlet into the
building.
• Four (4) feet from electric and gas meters, regulators
and relief equipment.
EVAPORATOR
SECTION
DOT PLUG
(For pressure
drop reading)
FILTER
ACCESS
40-1/2"
1" NPT FEMALE
COND. DRAIN
CONNECTION
OUTDOOR AIR
COMPARTMENT
ACCESS
3