5.3 Model conversion instructions

The model conversion instructions (below five instructions) which were added for CJ1M CPU Unit Ver. 3.0 or later
can be used with CJ2M CPU Units in the same way as CQM1H series CPU Units.
Those instructions are automatically converterd by executing change model (from CQM1H to CJ2M) on the
CX-Programmer Ver.5 or later (CX-Programmer Ver.5 or later supports functions of CJ1M CPU Unit Ver. 3.0).
Be sure to check the operation, since operation specifications including instruction execution time might differ.
Instructions
BLOCK
TRANSFER
SINGLE WORD
DISTRIBUTE
hDATA COLLECT
MOVE BIT
BIT COUNTER
Model conversion instruction
(CJ1M CPU Unit Ver.3.0 or
later and CJ2M CPU Units)
XFERC (565)
DISTC (566)
COLLC (567)
MOVBC (568)
BCNTC (621)
Corresponding instruction for
CQM1H
XFER (70)
DIST (80)
COLL (81)
MOVB (82)
BCNT (67)