Vitotronic 100, Type Hc1, For Constant Temperature Operation; Structure And Functions; Construction; Control Characteristics - Viessmann VITODENS 300 Datasheet

Gas fired condensing boiler 4.5 to 66.0kw as multi−boiler system up to 264kw
Hide thumbs Also See for VITODENS 300:
Table of Contents

Advertisement

Vitotronic 100 for constant temperature operation

Vitotronic 100, type HC1, for constant temperature operation

Integrated in Vitodens
H Electronic boiler control unit for
operating Vitodens at a constant boiler
water temperature

Structure and functions

Construction

The control unit comprises a basic unit,
electronic modules and a programming
unit.
The control unit contains the following:
System ON/OFF switch, digital display,
control thermostat, temperature limiter,
keys for
H Operating mode
H Boiler water and DHW temperature
H Emissions test function,
burner fault indication, burner fault reset,
integral diagnostic system and fuses.

Control characteristics

PI characteristics with modulating output.
Specification
Rated voltage:
230 V~
Rated frequency:
50 Hz
Rated current:
6 A
Safety class:
I
Protection:
IP X4 D to EN 60529,
safeguard through
design/installation
Function:
Type 1 B to EN 60730 1
Permissible
ambient temperature
H during operation: 0 to +40 ºC
Use in living space
and boiler rooms
(standard ambient
conditions)
H in storage
20 to +65 ºC
and transport:
Electronic control
thermostat
74 ºC (change not
setting:
possible)
Electronic temp.
limiter setting
81 ºC (change not
(heating mode):
possible)
Temperature
100 ºC (change not
limiter setting:
possible)
DHW temperature
setting range
H Gas fired
10 to 57 ºC
combi boiler:
H Gas fired boiler: 10 to 60 ºC
20
H A Vitotrol 100, type UTA or UTD is
required for room temperature−
dependent operation (according
to EnEV [Germany])
Summer mode
Heating program w
The burner starts only when the cylinder
needs reloading or when DHW is drawn
from a combi boiler.
Boiler temperature sensor
The boiler temperature sensor is
connected to the control unit and built
into the boiler.
Permiss. ambient
temperature
H in operation:
20 to +130 ºC
H in storage
20 to +170 ºC
and transport:
Frost protection
The frost protection function is active in
all heating programs.
The burner is switched ON when the
boiler water temperature reaches 5 ºC and
will be switched OFF again, when the
boiler water temperature reaches 15 ºC.
The circulation pump will be switched ON
simultaneously with the burner and
switched OFF after a delay.
To protect the system from frost, the
circulation pump may be started at
certain intervals (up to 24 times per day)
for periods of approx. 10 minutes.
H Integrated diagnostic system
H Integral cylinder thermostat
Cylinder temperature sensor
Standard delivery for
H Connection set for wall mounted DHW
cylinders (80 litres) (order separately)
H Connection set for DHW cylinders
installed below the boiler
(120 or 150 litres) (order separately)
H Connection set for DHW cylinders
installed adjacent to the boiler
(160, 200 or 300 litres) or alternative
DHW cylinders (order separately)
H Order the cylinder temperature sensor
for Vitodens 300 from 49 kW separately
(see page 21).
Cable length approx. 3.75 m, wired ready
to plug in
Protection:
IP 32
Permiss. ambient
temperature
H in operation:
20 to +90 ºC
H in storage
20 to +70 ºC
and transport:
Programming unit
H Display
H Display of temperatures and faults
H Coding display
VITODENS 300