Troubleshooting
12-2-11 O.C.(Over Current) error
1. Checklist :
1) Is the Shunt resistance value correct?
2) Is the condition of surrounding temperature abnormal overload?
3) Is there any problem as like the temperature sensor separation or measurement value error?
4) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after power off.
Is the O.C.(Over Current) error occurred?
Is the Shunt resistance value normal?
Is the interphase resistance value
of compressor (u↔v, v↔w, w↔u) normal?
Is the compressor body and
interphase resistance insulated?
Is the condition of
indoor/outdoor temperature normal load?
Is the position of temperature sensor
and the sensing value normal?
Is the connection cable for
the compressor and power terminal normal?
Exchange the PCB.
12-13
26005A(2)_1.indd
18
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
Yes
No
Yes
No
Yes
Terminate the service.
Exchange the PCB.
Exchange the Compressor.
Exchange the Compressor.
Restart after returning
to the normal load.
No
Is the O.C. error occurred again?
Correct the sensor position or
exchange the sensor.
Correct the cable connection.
Terminate
the service.