Outline Of Heating Operation - Mitsubishi Heavy Industries SRK25ZJ-S Technical Manual

Inverter wall mounted type residential air-conditioners (split system, air to air heat pump type)
Hide thumbs Also See for SRK25ZJ-S:
Table of Contents

Advertisement

(9) Outline of heating operation

(a)
Operation of major functional components in heating mode
Compressor
Indoor fan motor
Outdoor fan motor
4-way valve
(b)
Details of control at each operation mode (pattern)
1)
Fuzzy operation
Deviation between the indoor temperature setting correction temperature and the return air temperature is calculated in
accordance with the fuzzy rule, and used for control of the air capacity and the compressor speed.
Fan speed
Auto
HI
MED
LO
When the defrosting, protection device, etc. is actuated, operation is performed in the corresponding mode.
2)
Hot keep operation
If the hot keep operation is selected during the heating operation, the indoor blower is controlled based on the temperature
of the indoor heat exchanger (Th2) to prevent blowing of cool wind.
(c)
Defrosting operation
Starting conditions (Defrosting operation can be started only when all of the following conditions are met.)
1)
a)
After start of heating operation
When it elapsed 45 minutes. (Accumulated compressor operation time)
b)
After end of defrosting operation
When it elapsed 45 minutes. (Accumulated compressor operation time)
c)
Outdoor heat exchanger sensor (TH1) temperature
When the temperature has been below - 5ºC for 3 minutes continuously.
d)
The difference between the outdoor air sensor temperature and the outdoor heat exchanger sensor temperature
¡ The outdoor air temperature ≧ 0ºC : 7ºC or higher
¡ - 15ºC ≦ The outdoor air temperature < 0ºC : 4/15 × The outdoor air temperature + 7ºC or higher
¡ The outdoor air temperature < - 15ºC : - 5ºC or higher
0
-5
-10
-15
-20
-20
Thermostat ON
ON
ON
ON
ON
Model
SRK20ZJX-S
30~94rps
30~94rps
30~66rps
30~40rps
Defrost operation
start
-15
-10
-5
0
Outdoor air temperature (℃)
Heating
Thermostat OFF
OFF
ON(HOT KEEP)
OFF
(few minutes ON)
ON
(3 minutes ON)
SRK25ZJX-S
SRK35ZJX-S
30~102rps
30~115rps
30~102rps
30~115rps
30~72rps
30~76rps
30~42rps
30~46rps
5
10
61
-
-
'10 • SRK-T-098
Failure
OFF
OFF
OFF
OFF