LG CRNN Series Installation Manual page 59

Multi v air conditioner
Hide thumbs Also See for CRNN Series:
Table of Contents

Advertisement

Installation of Convertible Type Indoor Unit
2) Clamping of cables
1) Arrange 2 power cables on the control panel.
2) First, fasten the steel clamp with a screw to the inner boss of control panel.
3) For the cooling model, fix the other side of the clamp with a screw strongly.
For the heat pump model, put the 0.75mm
other boss of the control panel.
4) In Australia, the length of power supply cord measured from the entry of the power supply cord to the middle of live pin
on the power plug should be over 1.8m.
The power cord connected to the
indoor unit should be complied with
the following specifications
(Type H05VV-F(Indoor)
approved by HAR or SAA).
NORMAL CROSS-
SECTIONAL AREA
• 2.5mm
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of
wiring, be guided by the circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose
from vibrations to which the unit is subjected during the course of transportation. Check them
and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out
of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage
marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to
the normal function of a overload protection device.
• Proper starting power is not given to the compressor.
10) The means for disconnection from a power supply shall be incorporated in the fixed wiring and
have an air gap contact separation of at least 3mm in each active(phase) conductors.
cable(thinner cable) on the clamp and tighten it with a plastic clamp to the
2
The power connecting cable
connected between the indoor and
outdoor unit should be complied
with the following specifications
(Type H07RN-F approved by HAR or SAA).
2
CAUTION
NORMAL CROSS-
SECTIONAL AREA
2
• 2.5mm
Installation of Convertible Type Indoor Unit
The connecting cable connected
between the indoor and outdoor unit
should be complied with the
following specifications
(Type H07RN-F approved by HAR or SAA).
NORMAL
CROSS-
SECTIONAL
AREA
2
1.5mm
59