Heatilator HEIR36H Owner's Manual page 27

Hide thumbs Also See for HEIR36H:
Table of Contents

Advertisement

1. Top Vent - Horizontal Termination
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling fi restops.
• ALWAYS maintain specifi ed clearances around venting and fi restop systems.
• Install wall shield and ceiling fi restops as specifi ed.
Failure to keep insulation or other material away from vent pipe may cause fi re.
One Elbow
Note: Flue restrictor is permit-
ted ONLY on 30 ft. minimum
vertical runs with no elbows.
HEIR36 (NG/LP), HEIR42 (NG/LP),
HEIR50 (NG/LP)
V
Minimum
1
2 ft
610 mm
2.5 ft
762 mm
3 ft
914 mm
4 ft
1.2 m
5 ft
1.5 m
6 ft
1.8 m
7 ft
2.1 m
10 ft
3.0 m
20 ft
6.1 m
After V
= 6 ft then H
= 2 x V ft Maximum
1
1
V
+ H
= 60 ft Maximum
1
1
*when used with approved termination caps
Figure 7.3
H
1
H
Maximum
1
7 in*
178 mm
17 in.
432 mm
2 ft
610 mm
4 ft
1.2 m
9 ft
2.7 m
12 ft
3.7 m
14 ft
4.3 m
20 ft
6.1 m
40 ft
12.2 m
Heatilator • HEIR36, HEIR42, HEIR50 • 2285-900 Rev. F • 11/12
WARNING
WARNING! Risk of Fire!
• HEIR36(NG/LP), HEIR42(NG/LP) and HEIR50(NG/LP) models
require a minimum of 24 inches of vertical venting before attaching
any elbow to the appliance.
DO NOT attach elbow directly to the appliance.
V
1
27