Heat Controller HBH/V Compact Installation, Operation & Maintenance Manual page 38

Commercial horizontal & vertical packaged water-source heat pumps hbh & hbv compact horizontal & vertical hfc-410a units
Table of Contents

Advertisement

IOM Instructions
HBH/V CompaCt
Heat Controller, Inc.
Unit Operating Pressures and Temperatures
Table 8d: HB Series Typical Unit Operating Pressures and Temperatures (60 Hz-I.P. Units)
Table 9: Water Temperature Change Through Heat Exchanger
Rise, Cooling
Drop, Heating
Water Flow, gpm [l/m]
°F, [°C]
°F, [°C]
For Closed Loop: Ground Source or
9 - 12
4 - 8
Closed Loop Systems at 3 gpm per
[5 - 6.7]
[2.2 - 4.4]
ton [3.2 l/m per kW]
For Open Loop: Ground Water
20 - 26
10 - 17
Systems at 1.5 gpm per ton
[11.1 - 14.4]
[5.6 - 9.4]
[1.6 l/m per kW]