Unit Starting And Operating Conditions; Operating Limits - Heat Controller HBH/V Compact Installation, Operation & Maintenance Manual

Commercial horizontal & vertical packaged water-source heat pumps hbh & hbv compact horizontal & vertical hfc-410a units
Table of Contents

Advertisement

IOM Instructions

Operating Limits

Environment – Units are designed for indoor installation only. Never install units in areas subject to freezing or where
humidity levels could cause cabinet condensation (such as unconditioned spaces subject to 100% outside air).
Power Supply – A voltage variation of +/– 10% of nameplate utilization voltage is acceptable.
Determination of operating limits is dependent primarily upon three factors: 1) return air temperature. 2) water
temperature, and 3) ambient temperature. When any one of these factors is at minimum or maximum levels, the other
two factors should be at normal levels to insure proper unit operation. Extreme variations in temperature and humidity
and/or corrosive water or air will adversely affect unit performance, reliability, and service life. Consult Table 6a for
operating limits.
Table 6a: Operating Limits
TS
Operating
Starting Limits
Heating
Air Limits
39ºF [4ºC]
Min. ambient air, DB
Rated ambient air, DB
68ºF [20ºC]
Max. ambient air, DB
85ºF [29ºC]
Min. entering air, DB/WB
45ºF [7ºC]
Rated entering air, DB/WB
68ºF [20ºC]
80ºF [27ºC]
Max. entering air, DB/WB
Water Limits
Min. entering water
20ºF [-6.7ºC]
Normal entering water
30-70ºF [-1 to 21ºC]
Max. entering water
90ºF [32ºC]
1.5 to 3.0 gpm / ton
Normal Water Flow
[1.6 to 3.2 l/m per kW]
GR
Starting Conditions
Starting Limits
Heating
Starting conditions are based upon the following notes:
Air Limits
Min. ambient air, DB
39ºF [4ºC]
Rated ambient air, DB
68ºF [20ºC]
Notes:
85ºF [29ºC]
Max. ambient air, DB
1. Conditions in Table 6b are not normal or continuous operating conditions. Minimum/maximum limits are start-up
Min. entering air, DB/WB
60ºF [16ºC]
Rated entering air, DB/WB
68ºF [20ºC]
conditions to bring the building space up to occupancy temperatures. Units are not designed to operate under
Max. entering air, DB/WB
80ºF [27ºC]
Water Limits
these conditions on a regular basis.
20ºF [-7ºC]
Min. entering water
2. Voltage utilization range complies with AHRI Standard 110
Normal entering water
30-70ºF [-1 to 21ºC]
Max. entering water
90ºF [32ºC]
1.5 to 3.0 gpm / ton
Table 6b: Starting Limits
Normal Water Flow
[1.6 to 3.2 l/m per kW]
Commissioning Limits
Air Limits
Min. ambient air , DB
Rated ambient air , DB
Max. ambient air , D B
Min. entering air , DB/WB
Rated entering air , DB/WB
Max. entering air , DB/WB
Wa ter Limits
Min. entering water
Normal entering water
Max. entering water
Normal Water Flow
Normal W ater Flo w

UNIT STARTING AND OPERATING CONDITIONS

TT
TC
HB
Cooling
Cooling
Heating
Heating
45ºF [7ºC]
39ºF [4ºC]
45ºF [7ºC]
39ºF [4ºC]
80.6ºF [27ºC]
80.6ºF [27ºC]
68ºF [20ºC]
68ºF [20ºC]
110ºF [43ºC]
110ºF [43ºC]
85ºF [29ºC]
85ºF [29ºC]
65/50ºF [18/10ºC]
60/45ºF [16/7ºC]
45ºF [7.2ºC]
40ºF [4.4ºC]
80.6/66.2ºF [27/19ºC]
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
68ºF [20ºC]
95/75ºF [35/24ºC]
80ºF [27ºC]
100/75ºF [38/24ºC]
80ºF [27ºC]
30ºF [-1ºC]
30ºF [-1ºC]
20ºF [-6.7ºC]
20ºF [-6.7ºC]
50-110ºF [10-43ºC]
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
30-70ºF [-1 to 21ºC]
120ºF [49ºC]
120ºF [49ºC]
90ºF [32ºC]
90ºF [32ºC]
1.5 to 3.0 gpm / ton
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
[1.6 to 3.2 l/m per kW]
GS
TC
Cooling
Heating
Cooling
Heating
45ºF [7ºC]
45ºF [7ºC]
39ºF [4ºC]
39ºF [4ºC]
80.6ºF [27ºC]
80.6ºF [27ºC]
68ºF [20ºC]
68ºF [20ºC]
110ºF [43ºC]
85ºF [29ºC]
110ºF [43ºC]
85ºF [29ºC]
70/60ºF [21/16ºC]
70/60ºF [21/16ºC]
60ºF [16ºC]
60ºF [15.6ºC]
80.6/66.2ºF [27/19ºC]
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
68ºF [20ºC]
95/75ºF [35/24ºC]
95/75ºF [35/24ºC]
80ºF [27ºC]
80ºF [27ºC]
50ºF [10ºC]
30ºF [-1ºC]
50ºF [10ºC]
20ºF [-7ºC]
50-110ºF [10-43ºC]
60-90ºF [15 to 32ºC] 60-70ºF [15 to 21ºC]
30-70ºF [-1 to 21ºC]
110ºF [43ºC]
120ºF [49ºC]
90ºF [32ºC]
90ºF [32ºC]
1.5 to 3.0 gpm / ton
2.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
[2.7 to 3.2 l/m per kW]
TT/TS/TR/TC
HB
Rev.: 23 Jan., 2009B
Cooling
Heating
45ºF [7ºC]
39ºF [4ºC]
80.6ºF [27ºC]
68ºF [20ºC]
110ºF [43ºC]
85ºF [29ºC]
*50/45ºF [10/7ºC]
40ºF [4.5ºC]
80.6/66.2ºF [27/19ºC]
68ºF [20ºC ]
110/83ºF [43/28ºC]
80ºF [27ºC]
30ºF [-1ºC ]
20ºF [-6.7ºC]
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
120ºF [49ºC]
90ºF [32ºC]
1.5 to 3.0 gpm / to n
[1.6 to 3.2 l/m per kW ]
*If with active ClimaDry 70/61ºF (21/16ºC)
Rev.: 23 July, 2009B
HBH/V CompaCt
TS
Cooling
45ºF [7ºC]
80.6ºF [27ºC]
68ºF [20ºC]
110ºF [43ºC]
85ºF [29ºC]
60/50ºF [16/10ºC]
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
95/75ºF [35/24ºC]
80ºF [27ºC]
30ºF [-1ºC]
20ºF [-6.7ºC]
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
120ºF [49ºC]
90ºF [32ºC]
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
GR
Cooling
45ºF [7ºC]
80.6ºF [27ºC]
68ºF [20ºC]
110ºF [43ºC]
85ºF [29ºC]
70/60ºF [21/16ºC]
60ºF [16ºC]
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
95/75ºF [35/24ºC]
80ºF [27ºC]
30ºF [-1ºC]
20ºF [-7ºC]
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
120ºF [49ºC]
90ºF [32ºC]
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
Heat Controller, Inc.
Heating
Cooling
39ºF [4ºC]
45ºF [7ºC]
80.6ºF [27ºC]
110ºF [43ºC]
45ºF [7ºC]
65/50ºF [18/10ºC]
80.6/66.2ºF [27/19ºC]
95/75ºF [35/24ºC]
30ºF [-1ºC]
50-110ºF [10-43ºC]
120ºF [49ºC]
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
Heating
Cooling
39ºF [4ºC]
45ºF [7ºC]
80.6ºF [27ºC]
110ºF [43ºC]
70/60ºF [21/16ºC]
80.6/66.2ºF [27/19ºC]
95/75ºF [35/24ºC]
50ºF [10ºC]
60-90ºF [15 to 32ºC] 60-70ºF [15 to 21ºC]
110ºF [43ºC]
2.5 to 3.0 gpm / ton
[2.7 to 3.2 l/m per kW]
TC
Heating
39ºF [4ºC]
68ºF [20ºC]
85ºF [29ºC]
45ºF [7.2ºC]
68ºF [20ºC]
80ºF [27ºC]
20ºF [-6.7ºC]
30-70ºF [-1 to 21ºC]
90ºF [32ºC]
TC
Heating
39ºF [4ºC]
68ºF [20ºC]
85ºF [29ºC]
60ºF [16ºC]
68ºF [20ºC]
80ºF [27ºC]
50ºF [10ºC]
90ºF [32ºC]
Rev.: 23 Jan., 2009B